5.2 Selecting the Installation Location
5.2.1 This is guidance for installer to choose a suitable installation
location, to avoid potential damages to device and operators.
1) The wall selected to install the inverter must be strong and firm
enough to support and bear the weight of the inverter for a long
period time.
2) The location selected must be suitable for inverters' dimension. (Refer
to 3.3 Dimensions and Fig.5.2 Required Clearances)
3) Do not install the inverter on structures constructed of flammable or
thermo labile materials.
4) Never install the inverter in environment of little or no air flow, nor
dust environment.
5) The Ingress Protection rate is IP65 which means the inverter can be
installed outdoors and indoors.
6) Do not expose the inverter to direct sunlight, in order to avoid the
power and efficiency derating caused by excessive heating.
7) The ambient temperature of the inverter should be -25
℃
~+60
℃.
8) The installation location must be freely and safely to get at all times.
9) Vertically installation and make sure the connection of inverter must
be downwards. Never install horizontal and avoids forward and
sideways tilt.( Refer to drawings below)
13
14
When a photovoltaic panel is exposed to light, it generates a DC voltage.
When connected to this equipment, a photovoltaic panel will charge the
DC link capacitors.
Energy stored in this equipment's DC link capacitors presents a risk of
electric shock. Even after the unit is disconnected from the grid and
photovoltaic panels, high voltages may still exist inside the PV-Inverter.
Do not remove the casing until at least 5 minutes after disconnecting all
power sources.
Although designed to meet all safety requirements, some parts and
surfaces of Inverter are still hot during operation. To reduce the risk of
injury, do not touch the heat sink at the back of the PV-Inverter or nearby
surfaces while Inverter is operating.
Fig5.1
11) Do not install the inverter near television antenna or any other antennas
and antenna cables.
12) Do not install the inverter in living area, the noise caused by the
machine may affect on daily life.
13) For security reasons, don't install the inverter in place where the
children can reach.
10) Notice the minimum clearances of the inverter. (Refer to 3.3 Dimensions
and Fig.5.2 Required Clearances).
Fig5.2
5.3 Installation guide
5.3.1 Mounting Expansion Bolt
DANGER
In order to avoid electrical shock or other injury, inspect existing
electronic or plumbing installations before drilling holes.
To mount the inverter on the wall, we should mount expansion bolt to the
wall firmly first.