21
22
WARNING
Improper operation during the wiring process can cause fatal injury to
operator or unrecoverable damage to the inverter. Only qualified
personnel can perform the wiring work.
Risk of damage to the inverter.
If the voltage of the PV modules exceeds the maximum input voltage of
the inverter, it can be destroyed by the overvoltage. This will void all
warranty claims.
Do not connect strings to the inverter that have an open-circuit voltage
greater than the maximum input voltage of the inverter.
To reduce the risk of electric shock, avoid touching the live components
and treat the terminals carefully.
Information
Please use the same brand male and female PV connectors.
Under any conditions the total circuit current should never exceed the
Max. Current.
NOTICE
Excessive voltages can destroy the measuring device
Only use measuring devices with a DC input voltage range up to at least
1000 Vdc.
1 Check the connection cables of the PV modules for correct polarity and make sure
that the maximum input voltage of the inverter is not exceeded.
2 The diagram drawing of DC side is shown as below, notice that the connectors
are in paired (male and female connectors).
Fig 6.1
F i g 6 . 2