49
50
10
Decommissioning
10.1 Dismantling the Inverter
1. Disconnect the inverter as described in section 7.
2. Remove all connection cables from the inverter.
CAUTION
Danger of burn injuries due to hot enclosure parts!
Wait 20 minutes before disassembling until the housing has
cooled down.
3. Screw off all projecting cable glands.
4. Lift the inverter off the bracket and unscrew the bracket screws.
10.2 Packing the Inverter
If possible, always pack the inverter in its original carton and secure it with tension
belts. If it is no longer available, you can also use an equivalent carton. The box must
be capable of being closed completely and made to support both the weight and the
size of the inverter.
10.3 Disposing of the Inverter
Do not dispose of faulty inverters or accessories together
with household waste. Please accordance with the disposal
regulations for electronic waste which apply at the
installation site at that time. Ensure that the old unit and,
where applicable, any accessories are disposed of in a
proper manner.
11
Specification
11.1 Specification of TL3-S
Model
7000TL3-S
8000TL3-S
9000TL3-S
Specification
Input data
Max. DC power
8400W
9600W
10800W
Max. DC voltage
1000V
1000V
1000V
Start Voltage
160V
160V
160V
PV voltage range
160V-1000V
160V-1000V
160V-1000V
MPP voltage range/
DC nominal voltage
200V-1000V /600V
Max. PV Isc
16A/16A
16A/16A
16A/16A
Number of independent
MPP trackers/strings per
MPP tracker
2/1+1
Full load voltage
range
320V-850V
360V-850V
400V-850V
Max. input current
11.5A/11.5A
11.5A/11.5A
11.5A/11.5A
Backfeed current
0A
0A
0A
Output (AC)
Inrush current
<
15A
<
15A
<
15A
Max output fault
current
Max output overload
protection
Nominal AC voltage
range
AC grid frequency
50/60Hz
50/60Hz
50/60Hz
AC grid frequency range
44-55Hz/54-65Hz
Nominal AC voltage
230V/400V
230V/400V
230V/400V
Max. output current
11.7A
13.3A
15A
Rated AC output power
7kW
8kW
9kW
Max AC apparent power
7.7kVA
8.8kVA
9.9kVA
33A
33A
33A
16A
20A
25A
184~275V
184~300V
184~300V
2/1+1
2/1+1