53
54
Model
10000TL3-S
11000TL3-S
12000TL3
Specification
Input data
Max. DC power
12000W
14400W
14400W
Max. DC voltage
1000V
1000V
1100V
Start Voltage
160V
160V
160V
PV voltage range
160V-1000V
160V-1000V
160V-1000V
MPP voltage range/
DC nominal voltage
200V-1000V /600V
Max. PV Isc
16A/16A
16A/16A
16A/16A
Number of independent
MPP trackers/strings per
MPP tracker
2/1+1
2/1+1
2/1+1
Full load voltage
range
450V-850V
450V-850V
550V-850V
Max. input current
13A/13A
13A/13A
11.5A/11.5A
Backfeed current
0A
0A
0A
Output (AC)
Inrush current
<
15A
<
15A
<
15A
Max output fault
current
Max output overload
protection
Nominal AC voltage
range
AC grid frequency
50/60Hz
50/60Hz
50/60Hz
AC grid frequency range
44-55Hz/54-65Hz
Nominal AC voltage
230V/400V
230V/400V
230V/400V
Max. output current
16.7A
18.3A
19A
Rated AC output power
10kW
11kW
12kW
Max AC apparent power
11kVA
12.1kVA
13.2kVA
33A
33A
44A
25A
25A
25A
184~300V
184~300V
184~275V
Efficiency
Max efficiency
98.3%
98.3%
Euro-eta
98%
97.8%
MPPT efficiency
99.5%
99.5%
Power factor at rated power
1
1
1
Adjustable displacement
power factor
THDi @Full load&THDv<1%
0.8leading - 0.8laging
AC grid connection type
<
3%
<
3%
<
3%
3W+N+PE
3W+N+PE
3/N/PE
Protection devices
DC reverse polarity
protection
yes
yes
yes
DC switch for each MPPT
yes
yes
yes
Output AC overcurrent
protection
yes
yes
yes
Output AC overvoltage
Protection - Varistor
yes
yes
yes
Ground fault monitoring
yes
yes
yes
Grid monitoring
yes
yes
yes
Integrated all-pole
sensitive
leakage current
monitoring unit
yes
yes
yes
General Data
Dimensions(W/H/D)
in mm
Weight
Operating
temperature range
–
25 °C ... +60 °C
(–13 °F ... +140 °F)
With derating above 45 °C(113 °F)
Noise emission (typical)
≤
35 dB(A)
480*448*200
22kg
22kg
23.5kg
Altitude
3000m
98.3%
98%
99.5%