10
9
3.4 Storage of Inverter
3.5 The advantage of the unit
3.3 Size and weight
More detail about the type label as the chart below:
Model
Height (H)
Width (W)
Depth (D)
Weight
Growatt 8000MTLP-S
Growatt 9000MTLP-S
Growatt 10500MTLP-S
734mm 28.9inch
734mm 28.9inch
734mm 28.9inch
361mm 14.2inch
361mm 14.2inch
361mm 14.2inch
249mm 9.8inch
249mm 9.8inch
249mm 9.8inch
28kg
28kg
28kg
If you want to storage the inverter in your warehouse, you should choose an
appropriate location to store the inverter.
Ø
The unit must be stored in original package and desiccant must be left in the
package.
Ø
The storage temperature should be always between -25
℃
and +60
℃
. And the
storage relative humidity can achieve to 100%.
Ø
If there are a batch of inverters need to be stored, the maximum layers for original
carton is four.
Ø
After long term storage, local installer or service department of GROWATT should
perform a comprehensive test before installation.
Ø
Maximum efficiency of 98.1%
Ø
Wide input voltage range from 100--600Vdc
Ø
Reactive power regulate
Ø
Integrated DC switch
Ø
Multi MPP controller
Ø
DSP controller
Ø
Sound control
Ø
Multi communication pattern
Ø
Easy installation
Model Name
Max input DC voltage
Max input DC current
AC nominal voltage
AC grid frequency
Max. apparent power
AC normal output current
Power factor
Environmental
Protection
Rating
Operation Ambient
temperature
600V
12.5A/12.5A/25A
220V
220V
220V/230V
60 Hz
60 Hz
50/60 Hz
8800VA
9900VA
10500VA
36.4A
40.9A
47.7A
0.8leading…0.8lagging
IP65
-
25...+60
℃
(-13...+ 140°F)
with derating above 45°C
(
113°F
)
Growatt
8000MTLP-S
Growatt
9000MTLP-S
Growatt
10500MTLP-S
PV voltage range
100V~600V
Information
After long term storage, the Real Time Clock of the inverter maybe
not correct, it will cause the energy produced today (E_today) error,
you need to set the time and date, refer to clause 7.2.5 setting data
and time.