13
Recommended Diameter of Wire
Model
Recommended
output
current(A)
Output
voltage(V)
length≤
30m
length≤
60m
length≤
90m
length≤
120m
length≤
150m
length≤
180m
length≤
210m
750TL2-HV
4.2A (3PH) /
5.1 (1PH)
220V
1
1.5
2.5
4
4
4
6
1500TL2-HV
7.5A (3PH) /
10.2A (1PH)
220V
1.5
2.5
2.5
6
6
6
6
2200TL2-HV
10A (3PH) /
14 (1PH)
220V
2.5
2.5
4
6
6
6
6
4000TL2-HV
16A (3PH) /
25 (1PH)
220V
4
4
6
8
8
8
8
Units: mm
2
Notice: The environment temperature for the above recommended wire dimension should ≤50°C.
Notice: Large-power wall-mounted model uses multiple-channel DC input. The dimension of DC wire of each
channel shall be selected according to the above table.