17
Debugging Guidance
Before setting the parameters, please make sure all the wiring is correct.
a.
Set P00.01=0, to set as manual operation mode .
b.
Set the motor type through P00.02:0 indicates 3PH motor and 1 indicates 1PH motor.
c.
Set water pump nameplate parameters: P02.01 motor rated power value; P02.02 motor rated
frequency value; P02.04 motor rated voltage value; P02.05 motor rated current value.
d.
Water output test of pump
Click the run button to observe the running frequency and water output.Under the normal strong light
condition,if the operation frequency of three-phase motor is low or the water volume is small,it
indicates that the motor line may be connected reversely,so it is necessary to set function code
P00.13=1 or exchange the wiring of two motor lines.
e.
After finishing parameter setting of water pump, set P00.01=1. The operation code channel is altered
as original automatic mode instruction .
Notice:
If the inverter fails,set P00.18 to restore the factory settings.