2. Waiting: When the PV string DC voltage is greater than 100V, Inverter enters
“waiting” state and attempts to connect to the grid.
3. Normal operation: When PV string DC voltage is greater than 150V, Inverter
operates in normal state.
8. INVERTER STATUS
Inverter is designed to be user-friendly; therefore, the status of the Inverter can be
easily understood by reading the information shown on the front panel display. All
possible messages are shown in the following table.
DISPLAY
OPERATION
system fault
Auto Test Failed
Auto Test do not pass
No AC Connection
No Utility, No Grid Connect
GFDI Fault
Leakage current too large
PV Voltage High
PV panel Voltage too high
AC V Outrange
Grid Voltage out of range
AC F Outrange
Grid Frequency out of range
Inverter fault
Error: 100
2.5V Reference Voltage Fault
Error: 101
Communication Fault
Error: 102
Consistent Fault
Error: 116
EEPROM Fault
Error: 117
Relay Fault
Error: 118
Init Model Fault
Error: 120
HCT Fault
Error: 121
Communication Fault
Error: 122
Bus Voltage Fault
Error: 123
Auto Test Fail
9. COMMUNICATIONS
9.1 Communications software instructions
Shine NET is a PC software that communicate with Shine Inverter to analyze the
inverter working state. It is convenient for you to know the inverter real time working
state and the history work information.
Spec: