6.1 Commission the Inverter

1 ) Remove all covers from the PV array.

2) Check the PV and AC voltage.

3 ) Plug in the PV input.

4 ) Turn on the DC switch.

                                      

5 ) If  the  inverter  is  connected  with  PV  panel  arrays  and  the  input  voltage  is  higher 
than  250Vdc,  while  the  AC  grid  is  not  connected  yet,  LCD  will  display  messages  in 
order as below:

Company info

 → 

Basic info 

 → 

State info

The LCD will display “ AC V outrange “at State info and the LED turns red.

Please  check  all  information  on  the  LCD,  operate  by  knocks  you  will  see  the 

different parameters.

Single knock to Light the backlight

  →  

State info (single knock) Input info    

  →    

(single knock) Output info   

6)  Turn  on  the  AC  breaker  between  inverter  and  grid,  the  system  will  operate 
automatically.

7)  Under  normal  operating  conditions,  the  LCD  displays  ‘Power:  xx.xx  Kw’  at  State 
info, this is the power feed into grid. The LED turns green.

8) Check the time and date of inverter as follow:

Single knock to Light the backlight 

 → 

State info (Thrice knock) 

 → 

 Inverter info 

(single  knock) 

  →  

System  Time(double  knock),  if  they  are  not  correct,  please  set 

them,  refer  to  refer  to  6.3.4  setting  inverter  time  or  6.4.3  text  line  d

setting  date 

and time.

9) Finish commissioning.

·

·

·

·

6.2 Operation Modes

Normal Mode

In this mode, the inverter works normally and LED turns green.

Whenever the DC voltage is higher than 300Vdc, inverter converts power to grid as 

generated by the PV panels;

Whenever the DC voltage is lower than 250Vdc, the inverter will work in waiting 

state  and  attempt  to  connect  the  grid.  In  waiting  state  the  inverter  consumes  just 
enough power generated by the PV panel to monitor the internal system.

Notes:  The  inverter  starts  up  automatically  when  DC  power  from  the  PV  panel  is 
sufficient.

Fault Mode

The  internal  intelligent  controller  can  continuously  monitor  and  adjust  the  system 
state.  If  inverter  finds  any  unexpected  conditions  such  as  system  fault  and  inverter 
fault, the fault information will be displayed on the LCD. In fault mode the LED turns 
red.

Notes: a) Detailed fault information refers to Chapter 9.1 ERROR messages displayed 
on LCD.

  b) When PV Isolation error occurred in SAA safety standard, the buzzer will give an 
alarm every fifteen seconds.

Shutdown Mode

Inverters  automatically  stop  running  during  periods  of  little  or  no  sunlight.  In 
shutdown mode the inverters take no power from the grid and panel, and the LCD 
and LED turns off.

Notes: If the PV string DC voltage is too low, the inverter will also turn to Shutdown 
Mode.

Derating mode

When  AC  frequency  is  higher  than  50.3Hz(settable),  the  inverter  will  derate  its 
output power according to the rule. 

When user set the output limit command to the inverter, the inverter will also limit 
the output according to the setting.

In this derating mode, the LCD will show “DERATING”.

·

·

Summary of Contents for 30000 TL3

Page 1: ...LTD 1st East 3rd Floor Jiayu Industrial Zone Xibianling Shangwu Village Shiyan Baoan District Shenzhen P R China 86 755 2747 1900 86 755 2749 1460 info ginverter com Www ginverter com T F E W GR UM 0...

Page 2: ...or fitness for any particular purpose All such warranties are expressly disclaimed Neither Shenzhen Growatt New Energy Technology Co Ltd nor its distributors or dealers shall be liable for any indirec...

Page 3: ...PPT of the Growatt TL3 6 6 Communication Start up and Shut down the inverter 7 7 1 Start Up the inverter 7 2 Shut down the Inverter Maintenance and Cleaning 8 Trouble shooting 9 10 1 Dismantling the I...

Page 4: ...o observe these instructions For possible changes in this manual SHENZHEN GROWATT NEW ENERGY TECHNOLOGY CO LTD accepts no responsibilities to inform the users 1 1 3 Storage of the manual 1 1 4 Additio...

Page 5: ...ains Growatt TL3 series inverters or any other Growatt inverters the system designing software ShineDesign download from site www ginverter com will provide adequate supports AC Abbreviation for Alter...

Page 6: ...Assembly Warnings absence of any transport or handling damage which could affect insulation integrity or safety clearances failure to do so could result in safety hazards Unauthorized removal of nece...

Page 7: ...watt TL3 series inverters need install a separate energy meter The energy produced is compensated at a rate depending on the electric power company 2 5 Operation Warnings during operation Although des...

Page 8: ...of connection for grounding protection Operation after 5 minutes Direct Current DC Alternating Current AC EU waste electrical and electronic equipment WEEE label Product Description 3 3 1 Inverter ove...

Page 9: ...discover any visible damage to the inverter We will be glad to assist you if required When transporting the inverter the original or equivalent packaging should to be used and the maximum layers for o...

Page 10: ...RF Ethernet Wi Fi Wide PV voltage range 180V 1000V The maximum efficiency is 98 2 IP65 environmental protection Remote update capability Easy to install Fig 4 1 Item A B C D E F G H I Quantity 1 1 1...

Page 11: ...after the unit is disconnected from the grid and photovoltaic panels high voltages may still exist inside the PV Inverter Do not remove the casing until at least 5 minutes after disconnecting all pow...

Page 12: ...verter should be 25 60 The installation location must be freely and safely to get at all times Vertically installation and make sure the connection of inverter must be downwards Never install horizont...

Page 13: ...he bracket is firmly mounted on the wall then mount the inverter on the bracket Rise up the Growatt TL3 a little higher than the bracket Considering the weight of Growatt TL3 you need to hang on the i...

Page 14: ...n or snow to extend the inverter service life despite the IP65 protection degree Exposure to the sunlight may cause additional internal heating which will cause power derating Fig 5 7 Fig 5 8 More tha...

Page 15: ...rrent in the event of a malfunction in the original protective conductor For installation countries falling within the scope of validity of the IEC standard 62109 you must Installthe protective conduc...

Page 16: ...verter NEVER connect or disconnect the DC connectors under load Improper operation during the wiring process can cause fatal injury to operator or unrecoverable damage to the inverter Only qualified p...

Page 17: ...000 TL3 33000 TL3 40000 TL3 Max current 35A 38A 38A 5 In order to seal the inverter all unneeded DC inputs must be closed with sealing plugs Cable requirements 30000 TL3 33000 TL3 40000 TL3 Model 2 05...

Page 18: ...er should not be connected to PE 5 5 Grid Type 5 5 1 Common grid type For TT grid mode the valid value of the Neutral to PE voltage should be less than 30 V Based on the local GRID standards it may se...

Page 19: ...Whenever the DC voltage is higher than 300Vdc inverter converts power to grid as generated by the PV panels Whenever the DC voltage is lower than 250Vdc the inverter will work in waiting state and at...

Page 20: ...played can be changed by knock you can also change some inverter parameters by knock Fig 6 3 1 Fig 6 3 2 Note have been preset in factory and you don t need to operate this step any more If you have o...

Page 21: ...ht off After the power on information is displayed automatically and the backlight turns off the LCD display will switch to the following Interface 1 There are 4 interfaces which can be displayed in t...

Page 22: ...aximum energy yield of one hour Power curve The daily energy yield curve 6 3 2 3 Connecting messages When inverter started to connect to grid the following message will appear on LCD screen See Fig6 3...

Page 23: ...rameters setting First level menu It is a little bit different to enter the first level menu note that using thrice knock to enter first level menu instead of double knock Fig 6 3 14 is the interface...

Page 24: ...ut current for each MPP tracker PV input power for each MPP tracker Inverter output parameters AC output voltage for each phase AC output current for each phase AC output power for each phase Third le...

Page 25: ...rd level menu interface of working information State information First level menu Second level items Item explanation No xxxxxxxxxx Model xxxxxxxxxx Main Ver xxxxxx Comm Ver xxxxxx Serial number of th...

Page 26: ...ly if user saves save the choice by double knock and LCD displays Set OK The inverter provides five languages Italian English German Spanish and French The number on Set language interface is sequence...

Page 27: ...d bar of the graph represents the current unit of time Day h Week day Month M Year Y The top bar of the graph represents the maximum value of the graph values The daily graph is displayed by default Y...

Page 28: ...ine switch to the text as follow 2 Knock the enclosure lid twice and the text will show the language 3 You can choose the language by tripping the enclosure once the language includes English Deutsh E...

Page 29: ...once every time until the text line switch to the text as follow 2 Double knock the enclosure lid and switching to external wireless communication 3 Then knock the enclosure three times to confirm it...

Page 30: ...nd must not be used for billing purposes The inverter s measurement values are required for the operational control and to control the current to be fed into the electricity grid The inverter does not...

Page 31: ...6 2 Monitor the inverters The inverter provides RS485 interface and RS232 interface to communicate with remote PC or logger User can monitor the inverter state via the following types of communicatio...

Page 32: ...Through RS232 interface wireless module Data logger PC Through RS232 interface wireless module Data logger Internet Plan B 57 58...

Page 33: ...through the hole of cable gland and put the cable into the RS485 terminals fix all cables with screwdriver 1 to 1 3 to 3 2 to the shielding layer or no connection The type of cable is recommended as...

Page 34: ...ing fans failed Ventilation of installation location is poor Choose appropriate installation location before mounting Maintain fans and heatsink every half a year to reduce the power derating caused b...

Page 35: ...the fans in reverse order 9 1 Error Messages displayed on LCD An error message will be displayed on the LCD screen when a fault occurs The faults consist of system fault and inverter fault You may be...

Page 36: ...han 1 M If the error message is displayed despite the above checking passed contact Growatt 1 Restart invert 2 If error message still exists contact Growatt 1 Restart inverter 2 If error message still...

Page 37: ...Error 117 Error 119 Error 121 GFCI fault Control board has not received data from Communication board for 5S Restart inverter if problem still exist contact Growatt Restart inverter if problem still e...

Page 38: ...1000V 38A 38A 61 6kg 55 dB A Smart cooling IP 65 Transformerless 2000m without derating 0 100 551 740 276 mm 25 C 60 C with derating above45 C 0 5W Growatt 40000TL3 Datasheet H4 MC4 opt Screw termina...

Page 39: ...Shine Vision receiver Shine Vision emitter Internal fan of Growatt TL3 Outside fan of Growatt TL3 Communication interface Communication interface Communication data logger Communication data logger re...

Page 40: ...ter type 2 Modules information 3 Communication method 4 Serial number of Inverters 5 Error code of Inverters 6 Display of inverter Shenzhen Growatt New Energy Technology CO LTD 1st East 3rd Floor Jiay...

Reviews: