background image

2.2 Safety Precautions

The GROWATT UE series Inverters is designed and tested according to international
safety requirements; however, certain safety precautions must be observed when
installing and operating this inverter. Read and follow all instructions, cautions and
warnings in this installation manual. If questions arise, please contact Growatt's
technical services at +86 755 2747 1942.

2.3 Assembly Warnings

CAUTION

WARNING

The inverter may only be operated with a permanent connection to
the public power grid. The inverter is not intended for mobile use.
Any other or additional use is not considered the intended use. The
manufacturer/supplier is not liable for damage caused by such
unintended use. Damage caused by such unintended use is at the
sole risk of the operator.
Prior to installation, inspect the unit to ensure absence of any
transport or handling damage, which could affect insulation
integrity or safety clearances; failure to do so could result in safety
hazards.
Unauthorized removal of necessary protections, improper use,
incorrect installation and operation may lead to serious safety,
shock hazards or equipment damage.
In order to minimize the potential of a shock hazard due to
hazardous voltages, cover the entire solar array with dark material
prior to connecting the array to any equipment.

Grounding the PV modules: Comply with the local requirements for
grounding the PV modules and the PV generator.
Growatt recommends connecting the generator frame and other
electrically conductive surfaces in a manner which ensures
continuous conduction and ground these in order to have optimal
protection of the system and personnel.

2.4 Electrical Connection Warnings

DANGER

Some components in the inverter are live. Touching live components
can result in serious injury or death.
Danger to life due to high voltages in the inverter

All work on the inverter may be carried out by qualified

personnel only.

The appliance is not to be used by children or persons with

reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision
or instruction.
Children are forbidden to play around the Growatt inverter.

WARNING

Make all electrical connections (e.g. conductor termination, fuses,
PE connection, etc.) in accordance with prevailing regulations.
When working with the inverter powered on, adhere to all
prevailing safety regulations to minimize risk of accidents.
The Growatt UE series inverters may only be operated with PV
generators (modules and cabling) with protective insulation. Do not
connect any source other than PV modules to the Growatt UE series.
Systems with inverters typically require additional control (e.g.,
switches, disconnects) or protective devices (e.g., fuse, circuit
breaker) depending upon the prevailing safety rules.

CAUTION

House
grid:

Public
grid:

Energy flows into the house grid. The consumers connected,
for example, household devices or lighting, consume the
energy. The energy left over is fed into the public grid. When
the Growatt UE series inverters do not generate any energy,
e.g., at night, the consumers which are connected are supplied
by the public grid. The energy displayed on the LCD of inverter
is for reference only. When energy is fed into the public grid,
the energy meter spins backwards.

Energy is fed directly into the public grid. The Growatt UE
series inverters need install a separate energy meter. The
energy produced is compensated at a rate depending on the
electric power company.

2.5 Operation Warnings

WARNING

Ensure all covers and doors are closed and secure during operation.
Although designed to meet all safety requirements, some parts and
surfaces of Inverter are still hot during operation. To reduce the risk
of injury, do not touch the heat sink at the back of the PV-Inverter or
nearby surfaces while Inverter is operating.
Incorrect sizing of the PV plant may result in voltages being present
which could destroy the inverter. The inverter display will read the
error message “ PV Voltage High ”

Turn the rotary switch of the DC Disconnect to the Off position

immediately.

Contact installer.

The Growatt inverter is to be used solely to feed solar energy
converted photovoltaically into the public grid. The inverter is
suitable for mounting indoors and outdoors.
You can use the AC current generated as follows:

5

6

Summary of Contents for 4000UE

Page 1: ...stallation Operation Manual Shenzhen Growatt New Energy Technology CO LTD 1st East 3rd Floor Jiayu Industrial Zone Xibianling Shangwu Village Shiyan Baoan District Shenzhen P R China 86 755 2747 1942...

Page 2: ...g Index 1 2 3 4 2 2 Safety Precautions Installation 5 5 1 Safety instruction 5 2 Selecting the Installation Location 2 3 Assembly Warnings 2 4 Electrical Connection Warnings 2 5 Operation Warnings 2 6...

Page 3: ...Maintenance and Cleaning 8 8 1 Cleaning the Inverter 8 2 Checking the DC Disconnect Trouble shooting 9 10 1 Dismantling the Inverter 10 2 Packing the Inverter Decommissioning 10 10 3 Disposing of the...

Page 4: ...he Growatt UE Store this manual where accessible at all times 1 1 1 Validity 1 1 4 Additional Information For further information on special topics in the download area at www ginverter com 1 2 Symbol...

Page 5: ...r is not intended for mobile use Any other or additional use is not considered as intended use The manufacturer is not responsible for any damages resulting from unintended use Damage caused by such u...

Page 6: ...ledge unless they have been given supervision or instruction Children are forbidden to play around the Growatt inverter WARNING Make all electrical connections e g conductor termination fuses PE conne...

Page 7: ...ation is near radio or television receivers In this case the operator is obliged to take proper action to rectify the situation Possible damage to health as a result of the effects of radiation Do not...

Page 8: ...ax input current per string Max apparent power Norminal output current Norminal output voltage Protection Degree Operation Ambient Temperature AC Frequency range Power Factor Safety Level VDE 0126 1 1...

Page 9: ...tection Easy to install Unpacking 4 Unpacking 4 Before opening the packing box of Growatt UE please note that whether there are any visible external damages Once open the packing box please check the...

Page 10: ...the setup location is near radio or television receivers In this case the operator is obliged to take proper action to rectify the situation Never install the inverter near the sensitive equipment e g...

Page 11: ...ot install the inverter in living area the noise caused by the machine may affect on daily life 14 For security reasons don t install the inverter in place where the children can reach 5 3 Installatio...

Page 12: ...lance of the Growatt UE Hang the inverter on the bracket through the match hooks on bracket and the back of the inverter After confirming the inverter is fixed reliably fasten two M6 soket head cap sc...

Page 13: ...be installed the dimensions below should be considered Fig 5 6 19 20 Fig 5 4 Fig 5 5 5 4 Electrical Connections 5 4 1 Safety DANGER Danger to life due to lethal voltages High voltages which may cause...

Page 14: ...connection unit You must install a separate three phase miniature circuit breaker or other load disconnection unit for each inverter in order to ensure that the inverter can be safely disconnected und...

Page 15: ...he live components and treat the terminals carefully Information The PV modules should have an IEC61730 Class A rating Please use the same brand male and female PV connectors Under any conditions the...

Page 16: ...the PV grounding conductor and DC grounding conductor Ground kit If PV modules of the PV system require POSITIVE or NEGATIVE to connect to GROUND the output of inverter should connect to grid with an...

Page 17: ...f inverter as follow Single knock to Light the backlight State info Thrice knock Inverter info single knock System Time double knock if they are not correct please set them refer to 6 3 5setting inver...

Page 18: ...rmation After setting the DIP please power on the inverter and check the model display If the last character of the model name is corresponding to the country safety standard as the above table it mea...

Page 19: ...Greece GTXXXXXXX6 1 2 3 4 NO I VDE AR N 4105 GTXXXXXXX7 1 2 3 4 NO I UK_G83 GTXXXXXXX8 1 2 3 4 NO I Ireland GTXXXXXXX9 1 2 3 4 NO I CGC GTXXXXXXXA 1 2 3 4 NO I Denmark GTXXXXXXXB 1 2 3 4 NO I UK_G59...

Page 20: ...gle knock will switch LCD screen to a following interface 6 3 5 Data checking and parameters setting Cycle display It is a cycling display bit note that using signal knock to enter next page instead o...

Page 21: ...Parameters setting Fig 6 3 8 is the setting information Single knock the Text will display the setting Double knock the Text will display input123 000 Single knock to go back Setting page Double knoc...

Page 22: ...module utside he nverter o t i Bluetooth Bluetooth module utside he nverter o t i Inter Wireless Zigbee Zigbee module he nverter inside t i Wifi Wifi module he nverter inside t i Bluetooth Bluetooth...

Page 23: ...etting intern Wireless Bluetooth Knock three times to save RS232 Knock four times to exit the setting Inverter provides a system clock user must set the system time after installation as the historica...

Page 24: ...values The graph shows recent 12 months of power generation and the maximum value power of the 12 values The graph shows recent 16 years of power generation and the maximum value power of the 16 valu...

Page 25: ...ine switch to the text as follow Com Address 001 2 Double knock the enclosure lid and the lower number text 1 will flash 001 Com Address 002 3 If you want to change it single knock to change it from 0...

Page 26: ...on the inverter 2012 01 01 12 00 45 46 2 Double knock the enclosure lid and the text will switch to the year 2012 and the two lower numbers 2012 will flash you can change it by single knock 2014 01 0...

Page 27: ...brated meter 47 48 6 5 Double MPPT of the Growatt UE 6 6 Communication About the software of shinebus and the usage of it please download from the web www growatt comchannel to improve the energy util...

Page 28: ...for the inverter with the firmware after 0D37 0C30 Information If you want to update firmware online please disconnect AC breaker of the inverter first If you plan to update firmware via RS485 please...

Page 29: ...s module Data logger Internet 51 52 Plan B Shine Pano Line Computer Shine WebBox Line Computer Shine WebBox Router Internet Computer n Inverters RS 232 Wi Fi Shine WebBox Shine Pano Shine Net Computer...

Page 30: ...ding layer or no connection Definitions of RS485 PLUG standard as follows Pin4 RS485A Pin5 RS485B Pin6 No connection Pin7 Short with Pin8 Pin8 Short with Pin7 Pin1 RS485A Pin2 Shielding layer or no co...

Page 31: ...no connection The type of cable is recommended as KVVRP22 2 1 5mm2 Information Pull cables outwards to confirm whether they are installed firmly 3 4 Plug in two terminals Cover the fix board Informat...

Page 32: ...clogged To clean the air grills or heat sink Ventilation of installation location is poor Choose appropriate installation location before mounting 8 1 Cleaning the Inverter If the inverter is dirty tu...

Page 33: ...panels in each string Information concerning the PV panels If it is necessary to replace the unit please ship it in the original box 9 2 System fault System fault system faults are mainly caused by sy...

Page 34: ...ter if problem still exist update the firmware 2 Change control board or COM board if problem still exist contact Growatt Communication board has not received data from control board for 10 seconds Er...

Page 35: ...he size of the inverter 10 3 Disposing of the Inverter 10 3 Disposing of the Inverter Do not dispose of faulty inverters or accessories together with household waste Please accordance with the disposa...

Page 36: ...urrent protection yes yes yes Output AC overvoltage Protection Varistor yes yes yes Ground fault monitoring yes yes yes Grid monitoring yes yes yes Integrated all pole sensitive leakage current monito...

Page 37: ...ificates and approvals CE VDE0126 1 1 N4105 IEC 62109 AS3100 AS4777 EN61000 6 2 EN61000 6 3 2000m 6560ft without derating 11 2 DC connector info H4 Specification Contact size 2 5mm2 14AWG 4mm2 12 AWG...

Page 38: ...Shine Vision receiver Communication data logger receiver MR00 0000201 Shine Vision emitter Communication data logger emitter MR00 0000601 Zigbee Communication interface 200 0007000 Wi Fi Communication...

Page 39: ...technical problems concerning our products contact your installer or Growatt During inquiring please provide below information 1 Inverter type 2 Modules information 3 Communication method 4 Serial num...