20
19
Step 4: Make sure the wires are securely connected. The reference tightening torque
is 2.04 N.m.
WARNING! It's very important for system safety and efficient operation to use
appropriate cable for battery connection. To reduce risk of injury, please use the
proper recommended cable size as below.
Nominal Battery Voltage
Conductor cross-section (mm2)
AWG no.
48V
38
2
Load (AC Output) Connection
8
CAUTION:
operation, an additional disconnection device should be placed on in the building
wiring installation.
WARNING! It's very important for system safety and efficient operation to use
appropriate cable for AC connection. To reduce risk of injury, please use the proper
recommended cable size as below.
To prevent further supply to the load via the inverter during any mode of
Nominal Grid Voltage
Conductor cross-section (mm2)
AWG no.
208/220/230/240 VAC per phase
6
10
Model
Growatt 5000HYP
Step 1: Remove insulation sleeve 8 mm for three conductors. And shorten phase L
and neutral conductor N 3 mm. Refer to chart 4.
Step 3: Make sure the wires are securely connected.The reference tightening torque
is 0.82 N.m.
Step 2: Connect wires according to polarities indicated on terminal block. Be sure to
connect PE protective conductor ( ) first. Refer to Chart 5.
L
→
LINE (brown or black)
→
Ground (yellow-green)
N
→
Neutral (blue)