Installation
4
4.1 Selecting Mounting Location
Consider the following points before selecting where to install:
Do not mount the inverter on flammable construction materials.
Mount on a solid surface
This inverter can make noises during operation which may be perceived as a
nuisance in a living area.
Install this inverter at eye level in order to allow the LCD display to be read at all
times.
For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to
the side and approx. 50 cm above and below the unit.
Dusty conditions on the unit may impair the performance of this inverter.
The ambient temperature should be between 0°C and 40°C and relative humidity
should be between 5% and 85% to ensure optimal operation.
The recommended installation position is to be adhered to vertical.
For proper operation of this inverter, please use appropriate cables for grid
connection.
The pollution degree of the inverter is PD2. Select an appropriate mounting
location. Install the solar inverter in a protected area that is dry, free of excessive dust
and has adequate air flow. Do NOT operate it where the temperature and humidity is
beyond the specific limits. (Please check the specs for the limitations.)
Installation position shall not prevent access to the disconnection means.
This inverter is designed with IP20 for indoor applications only.
Regularly clean the fan filter.
·
·
·
·
·
·
·
·
·
·
·
·
·
1) PV connectors
2) AC output connectors
(Load connection)
3) Battery connectors
4) AC output connectors
5) RS-232 communication port
6) USB communication port
7) Intelligent slot
8) Grounding
9) LCD display panel (Please check
section 10 for detailed LCD operation)
10) Operation buttons
11) Dry contact
12) Battery thermal sensor
13)Emergency power off (EPO)
14)EMS port
15)DC Switch
16)Relay control port
17)Generator connectors
Installation to the wall should be implemented with the proper screws. After that,
the device should be bolted on securely.
The inverter only can be used in a CLOSED ELECTRICAL OPERATING AREA. Only
service person can enter into this area.
4.2 Preparation
WARNING!!
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE
SURFACE ONLY.
FIRE HAZARD.
WARNING!!
out from the package.
Remember that this inverter is heavy! Please be carefully when lifting
3.2 Product Overview