42
9.3 Checking the DC Disconnect
Check for externally visible damage and discoloration of the DC Disconnect
and the cables at regular intervals.If there is any visible damage to the DC
Disconnect, or visible discoloration or damage to the cables, contact the
installer.
Once a year, turn the rotary switch of the DC Disconnect from the On
position to the Off position 5 times in succession. This cleans the contacts
of the rotary switch and prolongs the electrical endurance of the DC
Disconnect.
10 Trouble shooting
Sometimes, the PV inverter does not work normally, we recommend the following
solutions for common troubleshooting. The following table can help the technician
to understand the problem and take action.
10.1 Warnings(W)
Warnings(W)
identify the current status of the Growatt MTL-S. Warnings do not
relate to a fault. When a (W) with a number after it appears in the display, it indicates
a Warning Code and is usually cleared through an orderly shutdown/re-set or a self
corrective action performed by the inverter. See the (W) codes in the following table.
Error message
Description
Suggestion
No AC Connection
No utility grid
connected or utility
grid power failure.
1.Check AC wiring
2.Contact Growatt.
AC V Outrange
Utility grid voltage
is out of
permissible range.
1.Check grid voltage.
2.If the error message still exists despite
the grid voltage being within the
tolerable range, contact Growatt.
AC F Outrange
Utility grid
frequency out of
permissible range.
1.Check grid frequency.
2.If the error message is displayed
despite the grid frequency being within
the tolerable range, contact Growatt.
Over Temperature
Temperature
outrange
1.
check the inverter operation state
2.
If the error message is displayed
still,please contact Growatt.
PV Isolation Low
Insulation problem
1.Check if panel enclosure ground
properly.