Growatt New Energy.CO.LTD
www.ginverter.com
31
details), and the grid is three-phase grid. Meanwhile, it shall be permitted by local power supply
department before install Grid-connected inverted power.
3)
Cable requirements
4.4.2 Preparation for electrical wiring
Before wiring, the users need to open the front door of inverter, and the specific procedures are as
follows:
Procedure 1:
Cut off the circuit breaker at DC&AC sides. As shown in Figure 4-4-2-1, move the
Grid switch and the PV switch to the state of "OFF".
Model
Growatt CP100
Grid Voltage Limit
360V-440V
Grid Frequency Limit
45HZ-55HZ
Cable (Cu)
Cable Diameter Requirements
(mm2)
Aperture
Model
Growatt CP100
PV Array PV+
70 mm² *2, or 120 mm²
;
Φ10
,
30N*m
PV Array PV-
70 mm² *2, or 120 mm²
Φ10
,
30N*m
Grid Phase A
95 mm²
Φ10
,
30N*m
Grid Phase B
Φ10
,
30N*m
Grid Phase C
Φ10
,
30N*m
Earth Wire
More than 50 mm²./Green and
Yellow
Φ10
,
30N*m
Communication
Wire
0.75mm²
,
shielded Twisted pair
/