8.1 Specification
Rating
Units
Value
PV input quantities:
V
MAX PV
(absolute maximum)
d.c. V
1000
PV input operating voltage range
d.c. V
450-1000
Maximum operating PV input current
d.c. A
250
I
SC PV
(absolute maximum)
d.c. A
250
Max. inverter backfeed current to the array
a.c. or d.c. A
250
a.c. output quantities:
Voltage (nominal or range)
a.c. V
400
Current (maximum continuous)
a.c. A
144
Current (inrush)
a.c. A (peak and duration)
500A/5mS
Frequency (nominal or range)
Hz
50
Power (maximum continuous)
W (or VA with PF)
100K
Power factor range
/
>0.9
Maximum output fault current
a.c. A (peak and duration), or
RMS
160 (RMS)
Maximum output overcurrent protection
a.c. A
160
Elect. protection class
/
Class I
Ingress Protection
/
IP20
Dimension of enclosure
mm
1100*850*1890
Environmental category
indoor
Suitability for wet locations
not
Pollution degree
Ⅱ
Overvoltage category
Category
Ⅲ
for AC output category
Ⅱ
for DC
input
Mains connection
Permanent connection
Transformer info
Isolating Transformer
Insulation class
Class H