Trouble Shooting

In  most  situations,  the  Inverter  requires  very  little  service.  However,  if  Inverter  is  not 
able  to  work  perfectly,  please  refer  to  the  following  instructions  before  calling  your 

local dealer.
Should any problems arise, the LED on the front panel will be red and the LCD displays 

the relevant information. Please refer to the following for a list of potential problems 

and their solutions.

SYSTEM FAULT

Ground I Fault

Isolation Fault

Grid Fault

1. The ground current is too high.
2. Unplug the inputs from the PV generator and check the peripheral AC system.
3. After the cause is cleared, re-plug the PV panel and check PV-Inverter status.
4. If the problem persists please call service.

1. Check the impedance is between PV (+) & PV (-) and the PV-Inverter is earthed. 
The impedance must be greater than 8M.
2. If the problem persists please call service.

1. Wait for 5 minutes, if the grid returns to normal, PV-Inverter automatically restarts.
2. Make sure grid voltage and frequency meet the specifications.
3. If the problem persists please call service.
4. Check grid usability.

No AC connection

1. Grid is not connected.
2. Check grid connection cables.

INVERTER FAILURE

PV Over Voltage

Consistent Fault

1.  Check  the  open  PV  voltage;  see  if  it  is  greater  than  or  too  close  to  450VDC.
2. If PV voltage is less than 450VDC, and the problem still occurs, please call local service.

1. Disconnect PV (+) or PV (-) from the input, restart the PV-Inverter.
2. If it does not work, call service.
If there is no display on the panel, please check PV-input connections. If the voltage is 

higher than 90V, call your local service.

During periods of little or no sunlight, the PV-Inverter may continuously start up and 

shut  down.  This  is  due  to  insufficient  power  generated  to  operate  the  control 

circuits.

Specifications 

 

7

 

Input Data

Max. input current 
/per string

Max. DC voltage

Max. DC power

PV voltage range 

MPP  voltage range

Number of MPP trackers/

strings per MPP tracker

Growatt1000

10A/10A

1300W

450V

70V-450V

110V-400V

1 / 1

Output Data

AC connection

Efficiency

MPPT efficiency

Nominal AC output power

Max. AC power

Max. output current

AC nominal voltage; range

AC grid frequency ; range

Phase shift (cos 

φ

THDI 

Max . efficiency

Euro-eta

99.5%

97%

95.5%

Protection Devices

Integrated all-pole sensitive 

leakage current monitoring unit

General Data

DC reverse polarity protection

AC short-circuit protection

Ground fault monitoring

Grid monitoring

Dimensions (W / H / D) in mm

Weight

yes

yes

yes

yes

yes

360/329/132

11.5 KG

Operating temperature range

–25°C..+60°C

Continuous full output power 
temperature range

–25°C..+50°C

Noise emission (typical)

25 dB(A)

Single phase

1000W

1100W

5.5A

220,230,240V; 

180Vac-280Vac

50Hz,60Hz;

±

5Hz

1

< 3%

Consumption: operating 

(standby) / night

Topology

<5W /< 0.5 W

transformerless

Cooling concept

No fan

Installation: Indoor/

Outdoors (IP65 electronics)

yes / yes

VDE 0126-1-1,N4105,
IEC 62109,G83,CE,
ENEL Guideline(CEI 0-21+A70)

Certificates and Approvals

20

Sungold 1000

10A/10A

1300W

450V

70V-450V

110V-450V

1 / 1

Single phase

1000W

1100W

5.5A

230V; 

207Vac~263Vac

50Hz,60Hz;±5Hz

1

< 3%

99.5%

97%

95.5%

yes

yes

yes

yes

yes

360/329/132

11.5 KG

–25°C..+60°C

–25°C..+50°C

≤ 

25 dB(A)

<5W /< 0.5 W

transformerless

No fan

yes / yes

AS 4777, AS/NZS 3100

Summary of Contents for Grid

Page 1: ...service ginverter com GR UM 001 09 GROWATT NEW ENERGY CO LTD No 28 Guanghui Road Longteng Community Shiyan Baoan District Shenzhen P R China ...

Page 2: ...irst check this manual before contacting your local dealer or representative Instructions inside this manual will help you solve most installation and operation difficulties CONTRNT INSTALLATION 2 1 Installation manual 2 2 Fixed on the wall 2 3 Connect to the grid AC utility 2 4 Connect to PV panel DC input 2 5 Checking 2 6 System diagram MODES OF OPERATION 3 1 Normal mode 3 2 Fault mode 3 3 Shutd...

Page 3: ...el is exposed to light it generates a DC voltage When connected to this equipment a photovoltaic panel will charge the DC link capacitors Energy stored in this equipment s DC link capacitors presents a risk of electric shock Even after the unit is disconnected from the grid and photovoltaic panels high voltages may still exist inside the PV Inverter Do not remove the casing until at least 10 minut...

Page 4: ...e upper straps of PV Inverter and ensure it fits on to the bracket Insert safety lock screws to the bottom leg to secure the inverter image 3 Check the secure mounting of the PV Inverter by trying to raise it from the bottom The PV Inverter should remain firmly attached Select the installation location so that the status display can be easily viewed Choose a strong mounting wall to prevent vibrati...

Page 5: ...cted and their output voltage is greater than 70Vdc but the AC grid is not yet connected inverter will start up automatically If it is the first time to power on the inverter after installation you may need to select a specific country Otherwise the interface will stay at the Please Select interface all the time There are eleven options to select as the list below Country Regulation Name options V...

Page 6: ...ctful please contact Growatt for specific software to clear and reset again When the selection is successful the inverter will reboot automatically 2 5 2 Commissioning After the inverter reboot LCD will produce the following messages in order Ser NO xxx xxxxx FW version Waiting No AC connection the display repeats NO Utility and LED will be red Close the AC breaker or fuse between PV Inverter and ...

Page 7: ...t controller can continuously monitor and adjust the system status If Inverter finds any unexpected conditions such as grid problems or internal failure it will display the information on its LCD and the LED will be red 3 3 Shutdown mode During periods of little or no sunlight Inverter automatically stops running In this mode Inverter does not take any power from the grid The display and LED s on ...

Page 8: ...RK 1 2 3 4 5 6 7 8 9 10 11 12 13 Etoday xx x KWh Eall xxx x KWh Tall xx x h PV xxx xxx B xxx AC xxxV F xx xHz SerNo xxxxxxxxxx Module PX UX MX SX FW version x x x Enable Auto Test Set Language Set LCD Contrast System F XXHz COM address xx 4 4 4 4 4 4 4 4 4 4 4 4 4 The energy today The total energy The total work time The PV1 PV2 voltage The AC voltage and frequency The serial number The inverter m...

Page 9: ...ndly therefore the status of the Inverter can be easily understood by reading the information shown on the front panel display All possible messages are shown in the following table DISPLAY OPERATION Auto Test Failed No AC Connection PV Isolation Low Residual I High Output High DCI PV Voltage High AC V Outrange AC F Outrange System fault Auto test do not pass No utility no grid connect Insulation ...

Page 10: ...eters 5 In Wave Data Interface Query the inverter real time and history power wave work data and error information 6 Multi languages English Simple Chinese French German Spanish and etc Support OS WinXP Vista win7 2000 2003 5 2 Monitor After setting the software the user can monitor the inverter The right side of the main interface is the detailed information of inverter 5 3 Detailed information D...

Page 11: ...g net plug RS485 terminals into the inverter tight waterproof connector lock waterproof device onto the inverter Note As to the connection between inverters please refer to the following figure 1 2 3 RS485 terminal of the inverter Com port of Shine WebBox RS 485 terminal of the inverter 1 1 2 3 1 2 3 RS 485 terminal of the inverter 2 1 2 3 1 2 3 As to the connection between inverter and Shine WebB...

Page 12: ...he panel please check PV input connections If the voltage is higher than 90V call your local service During periods of little or no sunlight the PV Inverter may continuously start up and shut down This is due to insufficient power generated to operate the control circuits Specifications 7 Input Data Max input current per string Max DC voltage Max DC power PV voltage range MPP voltage range Number ...

Reviews: