under any condition! Make sure the maximum open circuit voltage (Voc) 
of each PV string is less than 580 VDC for Growatt 4000, Growatt 4400, 
Growatt  5000,  Sungold  5000,less  than  500  VDC  for  Growatt  2000, 
Growatt  3000,Sungold  2000,  Sungold  3000  and  less  than  450  VDC  for 
Growatt 1500, Sunglow 1500, The length of input wire must be less than 
30m.

Use  H4  or  MC4  (Multi-contact)  connectors  for  PV  array  terminals.  Make 
sure DC switch is off before connecting.

Connect the positive negative terminals from the PV panel to positive (+) 
terminals and negative (-) terminals on the PV-Inverter. Each DC terminal 
on Inverter can withstand 20ADC.

Before  connecting  PV  panels  to  DC  terminals,  please  make  sure  the 
polarity  is  correct.    Incorrect  polarity  connection  could  permanently 
damage the unit. Checks short-circuit current of the PV string. The total 
short-circuit  current  of  the  PV  string  should  be  less  than  the  inverter’s 
maximum DC current.

High  voltages  exist  when  the  PV  panel  is  exposed  to  the  sun  .To  reduce 
risk  of  electric  shock,  avoid  touching  live  components  and  treat 
connection terminals carefully.

D

2.4

 

Connect to PV panel (DC input)

2.5 Checking

6

7

2.5.1 Country selecting

When the PV panels are connected and their output voltage is greater than 100Vdc 
but the AC grid is not yet connected, inverter will start up automatically. If it is the 
first time to power on the inverter after installation, you may need to select a specific 
country*  .Otherwise,  the  interface  will  stay  at  the  ‘Please  Select’  interface  all  the 
time. There are eleven options to select, as the list below.

Country/Regulation Name

options

VDE0126-1-1

Germany

UK_G83

Italy

France

Denmark

Belgium

Spain

Greece

Turkey

Hungary

// 

0

// 

1

// 

2

// 

3

// 

4

//

 

5

// 

6

// 

7

// 

8

// 

9

// 

10

Note:

 If the country you want to select is not in the above list, please directly select 

VDE0126-1-1.

Please finish the country selecting according to the following steps:

The  LCD  will  quickly  switch  to  and  stay  at  the  ‘Please  select’  interface 
after power on, as Fig 2-5-1.

A

Single  knock  on  the  LCD,  countries  will  vary  from  one  to  another  along 
the  above  list  order.  Fig  2-5-2  acts  as  an  example,  and  Germany  is  the 
second selection.

B

Fig 2-5-1

Fig 2-5-2

*

If  you  have  ordered  the  inverter  with  specific  country  settings,  the  parameters  have  been  preset  in  factory 
and you don't need to operate this step any more.

Summary of Contents for Growatt 1500

Page 1: ...service ginverter com GR UM 001 07 GROWATT NEW ENERGY CO LTD ...

Page 2: ...of this unit first check this manual before contacting your local dealer or representative Instructions inside this manual will help you solve most installation and operation difficulties CONTRNT INSTALLATION 2 1 Installation manual 2 2 Fixed on the wall 2 3 Connect to the grid AC utility 2 4 Connect to PV panel DC input 2 5 Checking 2 6 System diagram MODES OF OPERATION 3 1 Normal mode 3 2 Fault ...

Page 3: ...a DC voltage When connected to this equipment a photovoltaic panel will charge the DC link capacitors Energy stored in this equipment s DC link capacitors presents a risk of electric shock Even after the unit is disconnected from the grid and photovoltaic panels high voltages may still exist inside the PV Inverter Do not remove the casing until at least 10 minutes after disconnecting all power sou...

Page 4: ... ensure it fits on to the bracket Insert safety lock screws to the bottom leg to secure the inverter image 3 Check the secure mounting of the PV Inverter by trying to raise it from the bottom The PV Inverter should remain firmly attached Select the installation location so that the status display can be easily viewed Choose a strong mounting wall to prevent vibrations while inverter is operating 4...

Page 5: ...reat connection terminals carefully D 2 4 Connect to PV panel DC input 2 5 Checking 6 7 2 5 1 Country selecting When the PV panels are connected and their output voltage is greater than 100Vdc but the AC grid is not yet connected inverter will start up automatically If it is the first time to power on the inverter after installation you may need to select a specific country Otherwise the interface...

Page 6: ...ctful please contact Growatt for specific software to clear and reset again When the selection is successful the inverter will reboot automatically 2 5 2 Commissioning After the inverter reboot LCD will produce the following messages in order Ser NO xxx xxxxx FW version Waiting No AC connection the display repeats NO Utility and LED will be red Close the AC breaker or fuse between PV Inverter and ...

Page 7: ...t controller can continuously monitor and adjust the system status If Inverter finds any unexpected conditions such as grid problems or internal failure it will display the information on its LCD and the LED will be red 3 3 Shutdown mode During periods of little or no sunlight Inverter automatically stops running In this mode Inverter does not take any power from the grid The display and LED s on ...

Page 8: ... auto test Update Software The second line of LCD SerNo CYCLE DISPLAY DISPLAY TIME S REMARK 1 2 3 4 5 6 7 8 9 10 11 12 13 Etoday xx x KWh Eall xxx x KWh Tall xx x h PV xxx xxx B xxx AC xxxV F xx xHz SerNo xxxxxxxxxx Module PX UX MX SX FW version x x x Enable Auto Test Set Language Set LCD Contrast System F XXHz COM address xx 4 4 4 4 4 4 4 4 4 4 4 4 4 The energy today The total energy The total wo...

Page 9: ...he Frequency you need and wait until the display become dark Set contrast Knock to make the display bright knock to COM Address xx double knock to change the Address model knock to set address Inverter Status 4 Inverter is designed to be user friendly therefore the status of the Inverter can be easily understood by reading the information shown on the front panel display All possible messages are ...

Page 10: ...LED on the front panel will be red and the LCD displays the relevant information Please refer to the following for a list of potential problems and their solutions SYSTEM FAULT Ground I Fault Isolation Fault Grid Fault 1 The ground current is too high 2 Unplug the inputs from the PV generator and check the peripheral AC system 3 After the cause is cleared re plug the PV panel and check PV Inverter...

Page 11: ...rent per string Max DC voltage Max DC power PV voltage range MPP voltage range Number of MPP trackers strings per MPP tracker 20A 20A 4200W 580V 100V 580V 250V 500V 1 3 20A 20A 4600W 580V 100V 580V 250V 500V 1 3 20A 20A 5000W 5200W 580V 100V 580V 250V 500V 1 3 Output Data AC connection Efficiency MPPT efficiency Nominal AC output power Max AC power Max output current AC nominal voltage range AC gr...

Page 12: ...s yes yes yes 360 329 132 11 5 KG 360 329 132 11 7 KG 360 329 132 12 2 KG Operating temperature range 25 C 60 C 25 C 60 C 25 C 60 C Continuous full output power temperature range 25 C 50 C 25 C 50 C 25 C 50 C Noise emission typical 25 dB A 25 dB A 25 dB A Sungold 3000 Sungold 5000 20A 20A 5200W 580V 100V 580V 250V 500V 1 3 Single phase 1650W 1650W 8A 230V 207Vac 263Vac 50Hz 60Hz 5Hz 1 3 Single pha...

Reviews: