编号:
GR-UM-C -00
18
/
57
C. Connect the MP cable of the AC terminal with the matching M4 screw. After the RS485 is connected, lock the protective
casing on the inverter frame.
D. Lock the protective casing on the inverter frame and block the waterproof joint with fireproof mud to prevent water
ingress
.
NOTICE
Waterproof joints must be blocked with fireproof mud to prevent
water ingress.
6.2 DC Side Connection
DANGER
Before electrical connection, please ensure the inverter DC switch is at ‖OFF‖ also disconnect
AC switch, otherwise the high voltage from inverter may cause life risk.
Only trained authorized electrical technician can do the electric connection also please follow
the connection procedures in this manual along with local country’s regulations.
High voltage may cause electric shocks and serious injury please do not touch the inverter.
Please do not store inverter in area with flammable and explosive material.
Notice: The sunlight will generate voltage on the solar panels, after serial connection, the high voltage may injure personnel,
so before connect DC input cable you need cover solar panels with light-tight materials and make sure the inverter DC