Connecting
Cable
6
6.1 Connection on AC side
•Before electrical connection, please ensure the inverter DC switch is at
"OFF” also disconnect AC switch, otherwise the high voltage from inverter
may cause life risk.
•Only
trained
authorized
electrical
technician
can
do
the
electric
connection
also
please
follow
the
connection
procedures
in
this
manual
along
with
local
country's
regulations
.
•High voltage may cause electric shocks and serious injury please do not
touch the inverter.
•Please do not store inverter in area with flammable and explosive material.
•Each
inverter
must
install
one
AC
breaker
,
AC
breaker
is
forbidden
to
share
with
other
inverters
.
•It is forbidden to add load between inverter and breaker.
Preparation
before
connection
:
1>Disconnect inverter DC switch and AC breaker or switch.
2>When you lock the AC cable's screw, the torque force should be 30kgf·cm.
When you lock the cover screw, the torque force
should
be 20kgf·cm.
3>Measure the grid voltage and frequency, please refer to chapter 10.
AC
breaker
specification
:
15
16
DANGER
WARNING
Decisive Voltage Class (DVC) indicated for ports
Port Name
Class
AC
DC
DRMS
RS485&USB
C
C
A
A
图
5
.
12
图
5
.
13
图
5
.
14
Inverter
model
Breaker
model
MAX
100KTL3-X
LV
200A
/
400Vac
MAX
110KTL3-X
LV
250A
/
400Vac
MAX 120KTL3-X
LV
250A
/
400Vac
MAX
125KTL3-X
LV
250A
/
400Vac
MAX
133KTL3-X
LV
250A
/
400Vac
MAX
125KTL3-X
MV
200A
/
500Vac
MAX
136KTL3-X
MV
250A
/
500Vac
MAX
150KTL3-X
MV
250A
/
500Vac