background image

Product

 

Introduction

3.1 Appearance

Front

 

view

:

Bottom view(Termial):

Side

 

view:

Fig

 

3

.

1

Fig

 

3

.

3

6

5

Fig

 

3

.

2

Mark

Description

Mark

Description

A

Front

 

panel

H

COM

 

interface

B

LED

I

Corner

 

guard

C

PV

 

terminal

J

Waterproof

 

silicone

 

pad

D

DC

 

switch

K

Junction

 

Box

E

Breathing

 

valve

L

Ground

 

screw

 

hole

F

External

 

fans

M

Heat

 

sink

G

USB

 

interface

3.2 Basic Data

Model

Size(mm)

Weight

(

kg

)

Width

Height

Thickness

MAX

-

X

 

Series

 

I

nverter

970

640

345

84

MAX

-

X

 

Series Inverter

 

with

 

package

1095

765

500

98

3

.

3

 

Nameplate

Note:

 

Other models of MAX-X series share the same label design with MAX125KTL3-X 

LV, only with different model name and parameters, detail parameter please refer to 
specification in Chapter 10

.

Summary of Contents for MAX 100KTL3-X LV

Page 1: ...Energy Co Ltd 4 13 F BuildingA Sino German Europe IndustrialPark HangchengAve Bao anDistrict Shenzhen China T 86 755 27471942 E service ginverter com W www ginverter com Installation Operation Manual...

Page 2: ...roduction 4 Unpacking 5 Installation 5 1 Basic Installation Requirements 5 2 Installation Environment Requirements 5 3 Moving Requirements 5 4 Wall Mounted Installation 5 5 Installing the Inverter 3 1...

Page 3: ...ound Cables 6 Connecting Cables 11 Decommissioning 7 System Commissioning 12 Quality Assurance 7 1 Inverter Commissioning 7 2 Modes 7 3 LED display 8 1 Remote Data Monitoring 8 2 Local Data Monitoring...

Page 4: ...improper installation Growatt reserve the right to disclaim any warranty Ensure that the inverter is not connected to a power supply and is not power on before installation Before electrical connectio...

Page 5: ...hnician Burn Warning Do not touch a running inverter cause it generates high temperature on the case Protective Grounding Connect inverter to grounding bar Delay discharge Residual voltage exists afte...

Page 6: ...unction Box E Breathing valve L Ground screw hole F External fans M Heat sink G USB interface 3 2 Basic Data Model Size mm Weight kg Width Height Thickness MAX X Series Inverter 970 640 345 84 MAX X S...

Page 7: ...30V 230V 230V 480V 480V 480V Fig 3 5 Fig 3 6 AFCI Arc Fault Circuit Interrupter is a kind of circuit protection device the main function is to prevent the fire caused by fault arc The electrical insul...

Page 8: ...ld be from 30 60 H Inverter should be installed in a vertically or rear tilted surface please refer to following drawings Fig 5 1 I To ensure the inverter can work smoothly and easy for personnel to o...

Page 9: ...install multiple inverters on one surface inverters should be installed as following drawing D Do not install inverter into an enclosed space like following drawing Fig 5 6 12 11 5 3 Moving Requireme...

Page 10: ...be installed on solid walls with at least 100mm thickness 5 5 Installing The Inverter After the wall mount bracket has been firmly installed on the wall put the inverter on that plate 1 Use the rope...

Page 11: ...forbidden to share with other inverters It is forbidden to add load between inverter and breaker Preparation before connection 1 Disconnect inverter DC switch and AC breaker or switch 2 When you lock...

Page 12: ...approximately 30mm according to the specifications of the crimping terminal Use crimping tools to crimp the wires and terminals then connect the cables to the corresponding channels through the water...

Page 13: ...th inverter please make sure the positive pole and negative pole namely the solar panels positve pole connect to negative pole connect to Fig 6 5 6 Connect the positive and negative poles to inverter...

Page 14: ...hine WIFI X Shine 4G X Shine Link X and other optional monitoring modules to realize remote Monitoring function In addition you can also quickly upgrade the inverter software through the U disk Steps...

Page 15: ...are the wire That is the equipment grounding wire should be pulled separately and the wire diameter requirement 6mm when the safety interval distance S is satisfied 4 About the above lightning protect...

Page 16: ...to 8 2 download mobile APP ShinePhone and connect to inverter WIFI to enter local monitoring page this operation is performed by a professional 1 Click Parameters 2 Enter passwor When you use it for t...

Page 17: ...nal system status Note only when the PV modules supply enough power voltage 195Vdc then the inverter will start automatically Inverter intelligent control system will continuously monitor and adjust s...

Page 18: ...With AC voltage inverter is in a fault state The green light flashes slowly a n d t h e a l a r m o r f a u l t indicator light is steady red C Alarm or fault indicator light Inverter works normally...

Page 19: ...device and edit edit operation includes change device alias icon and delete device Fig 8 7 2 User can add datalogger at the datalogger list page to add a datalogger edit delete configure etc 3 User ca...

Page 20: ...to login page input the registered username and password click Sign In Fig 8 13 Fig 8 14 2 Add datalogger At Plant page click device manage then click add datalogger input the SN and valid code then s...

Page 21: ...Data reading A Basic production reading Energy today total production revenue today and accumulative revenue are showing on this page Fig 8 19 B Plant data page can check device power voltage curve b...

Page 22: ...or solar power plants with a high speed CPU and a stable Linux system that intelligently records the user s system characteristics Feature 1 A versatile and high performance communication data logger...

Page 23: ...or for operation Note The router needs to enable automatic IP assignment that is open the DHCP function C Enter the shinemaster IP address in the browser to enter the shinemaster built in page 2 Shine...

Page 24: ...toring mode for monitoring photovoltaic devices in the first drop down list of add or remove devices Fig 8 27 2 Select the type of photovoltaic device monitored in the second drop down list 3 Fill in...

Page 25: ...the first time please register the user name Enter the domain name access page as shown in figure 8 32 below Chinese user server domain name http server cn growatt com The domain name of the internat...

Page 26: ...you can get the wifi name of the collector by scanning the QR code or barcode The default password for WIFI is 12345678 If you have already connected you can click Skip to connect directly to the WIF...

Page 27: ...ipment can be modified according to the usage Fig 8 37 D Intelligent detection Detailed and accurate view of the device s detailed data and status Fig 8 38 Fig 8 36 Fig 8 37 E Intelligent I V curve sc...

Page 28: ...ick diagnosis I V curve diagnosis grid waveform THDV and cable impedance detection all at one click Fig 8 42 I High level setting According to the register address set parameters professionals J Devic...

Page 29: ...needs to be programming at last time Fig 8 44 8 2 2 U Disk Monitoring Fig 8 45 2 Fault Recording Create the bconfig txt file under the root of the U disk write the following content then insert the U...

Page 30: ...ance of load derating Inverter equipped with internal cooling fans when the internal temperature is too high the fans work in to reduce the internal temperature When the inverter is derating because o...

Page 31: ...replace with a cross screwdriver replace a new fan 4 Tidy up the wire 5 Install the fan fan guard fixed and the inverter again 9 2 Trouble Shooting 9 2 1 Warning It must be operated by well trained pr...

Page 32: ...02 AC F Outrange 1 Check the frequency is in the range of specification or not 2 Contact Growatt Warning 310 NE abnormal 1 Check if the neutral and ground cables are well connected 2 Contact Growatt W...

Page 33: ...t Error 405 Relay fault 1 Restart inverter 2 Contact Growatt Error 406 Init model fault 1 Restart inverter 2 Contact Growatt Error 407 AutoTest failure 1 Restart inverter 2 Contact Growatt Error Descr...

Page 34: ...V 198 5A 400V Power factor nominal 0 99 Max inrush current duration 20KA tr 8us tf 20us Max output facult current duration 400A 30us Adjustable power factor 0 8leading 0 8lagging THDi 3 AC grid connec...

Page 35: ...DC voltage 1100V Start voltage 195V Nominal voltage 600V 720V 720V 720V MPP voltage range 180V 1000V No of MPP trackers 10 No of PV strings per MPP trackers 2 Max input current per MPP trackers 32A Ma...

Page 36: ...f 20us Weight 84kg Operating temperature range 30 60 Altitude 4000m Internal consumption at 1W Note1 Topology Transformerless Cooling Smart air cooling Protection degree IP66 Relative humidity 0 100 D...

Page 37: ...ance with the disposal regulations for electronic waste which apply at the installation site at that time Ensure that the old unit and where applicable any accessories are disposed of in a proper mann...

Reviews: