Warning Code

Fault Discription

Suggestion

Warning 404

EEPROM abnormal.

1. Restart inverter.

2. If error message still exists,contact 

manufacturer.

Warning 405

DSP and COM firmware 
version unmatch

1. Check  the firmware version.
2. If error message still exists,contact 
manufacturer.

Warning 406

Boost module error

1. Restart inverter

2. If error message still exists, contact 

manufacturer.

Warning 407

NTC Temperature too 
high or NTC is broken

1. Restart inverter
2. If error message still exists, contact 
manufacturer.

Warning 408

NTCBroken

1. Restart inverter
2. If error message still exists, contact 
manufacturer.

Warning 409

CT Connect abnormal

1. Check the CT connect Whether it is 
correct or not.
2. If error message still exists, contact 
manufacturer.

13.2.2 Error code

Error Code

Fault Discription

Suggestion

Error 200

AFCI Fault

1. After shutdown,Check the panel terminal.
2. Restart inverter.
3. If error message still exists,contact 
manufacturer.

Error 201

Leakage current too 
high

1. Restart inverter.
2. If error message still exists,contact 
manufacturer.

Error 202

The DC input voltage is 
exceeding the maximum 
tolerable value

1. Immediately disconnect the DC switch and 
check the voltage
2. If the fault code still exists after the 
normal voltage is restored, contact 

manufacturer

Error 204

PV Reversed

1. After shutdown,Check the inverter 
terminal.

2. Restart inverter.
3. If error message still exists,contact 
manufacturer.

Error Code

Fault Discription

Suggestion

Error 300

AC V Outrange

1. Check grid voltage.
2. If the error message still exists despite the 
grid voltage being within the tolerable 
range, contactmanufacturer.

Error301

AC terminals reversed

1: Check AC terminals

2: If error message still exists, contact 

manufacturer.

Error 302

No AC Connection

1. After shutdown,Check AC wiring.
2. If error message still exists,contact 
manufacturer.

Error 303

PE abnormal

1. Check PE,to ensure that the PE line 

contact good.

2. If error message still exisits,contact 

Manufacturer

Error 304

AC F Outrange

1. Restart inverter.
2. If error message still exists,contact 
manufacturer.

Error 305

Over Load Fault

1. Check whether output load over range; If 

load too large, please reduce load.

2. If error message still exists, contact 

manufacturer.

Error 306

CT LN Reversed

1: After shutdown

Check the SP-CT 

connection.
2: If error message still exists,contact 
manufacturer.

Error 307

Communication 
fault,M3 didn't receive 
SP-CT data

1: Check communication wire
2: If error message still exists,contact 
manufacturer.

Error 308

Communication 

fault;Pairing time too 

long

1: Restart pairing

2: If error message still exists,contact 

manufacturer.

Error 400

DCI bias abnormal

1. Restart inverter

2. If error message still exists, contact 

manufacturer.

Error 401

DC Voltage High Fault

1. Restart inverter.
2. If error message still exists,contact 

manufacturer.

Error 402

Output DC current too 

high

1. Restart inverter.

2. If error message still exists,contact 

manufacturer.

Summary of Contents for MID 10KTL3-X

Page 1: ...nzhen P R China No 28 Guangming Road Shiyan Street Bao an District Shenzhen P R China 86 755 2747 1942 www ginverter com www ginverter com T E W service ginverter com service ginverter com 86 755 2747...

Page 2: ...2 1 Foreword 2 2 Applicable personnel 2 3 Product overview and features 2 4 Safety instructions 1 1 Validity 1 2 Target Group 1 3 Additional information 3 Product Description 4 Unpacking and Inspecti...

Page 3: ...ubleshooting 7 Debugging 14 Specification 8 1 Normal mode 8 2 Failure mode 8 3 Shutdown mode 9 1 Boot display 9 2 OLED display wake up 9 3 Touch operation 11 1 Start the inverter 11 2 Shut down the in...

Page 4: ...refully before using this product Any changes to this manual by Growatt New Energy will not be notified to the user 2 2 Applicable Personnel The inverter must be installed by a professional electricia...

Page 5: ...V modules Otherwise in the sunlight the voltage at the component terminals is high which poses a personal danger Make sure that the input DC voltage does not exceed 550V under any circumstances Higher...

Page 6: ...t operating state of the inverter red fault green normal operation Flashing red light warning Flashing green light Update program 3 2 Dimensions Size and weight Model Height H Width W Depth D Weight M...

Page 7: ...nverter for a long time refer to the specifications in Chapter 12 for the weight of the inverter The installation location must match the size of the inverter Do not install the inverter on a building...

Page 8: ...Installation Environment Make sure that the inverter is installed in a suitable place and is not allowed to be installed in a closed box fig5 4 Closed box In order to reduce the inverter load and ext...

Page 9: ...h of the inverter is in the OFF state and that the AC side is open otherwise the high voltage of the inverter may be life threatening Each inverter must be independently installed with an AC circuit b...

Page 10: ...er model Switch specification Inverter model Switch specification MID 6KTL3 XL 25A 127V MID 8KTL3 XL 32A 127V MID 10KTL3 XL 40A 127V MID 11KTL3 XL 40A 127V MID 12KTL3 XL 50A 127V MID 10KTL3 X 32A 230V...

Page 11: ...PV ground please turn on the low frequency isolation transformer after the output is connected otherwise the inverter will be damaged If it is measured that there is a stable non zero DC voltage betw...

Page 12: ...allation instructions 2 Push the threaded sleeve into the socket and tighten the waterproof gland fig6 9 Quick installation instructions Ka 3 Dock the client to the inverter plug until both are tightl...

Page 13: ...real time When the inverter monitors any unexpected conditions such as system failure and inverter failure the fault information will be displayed on the display In the fault mode the inverter indica...

Page 14: ...ic CT Off grid setting Enable Country Region VDE0126 Country Region VDE0126 Country Region G99 Country Region N4105 Country Region G98 Country Region Ireland Country Region EN50438 Country Region Belg...

Page 15: ...er 2 Close the DC switch when the input PV voltage is higher than 250Vdc and the inverter will start automatically Start and Shut Down the Inverter 11 11 1 Start the inverter 11 2 Shut down the invert...

Page 16: ...ew fan 5 Reinstall the fan mounting plate and inverter Troubleshooting 13 PV inverters sometimes do not work properly we recommend the following solutions to eliminate common faults The table below he...

Page 17: ...anufacturer 13 2 Syetem error 13 2 1 Warning code Warning Code Fault Discription Suggestion Warning 300 No Utility 1 Please confirm grid is lost or not 2 If error message still exists contact manufact...

Page 18: ...r 3 If error message still exists contact manufacturer Error Code Fault Discription Suggestion Error 300 AC V Outrange 1 Check grid voltage 2 If the error message still exists despite the grid voltage...

Page 19: ...art inverter 2 If error message still exists contact manufacturer Error 414 EEPROM fault 1 Restart inverter 2 If error message still exists contact manufacturer Error 415 Internal power test fail PV P...

Page 20: ...ctor 0 8Leading 0 8Lagging THDi 3 AC grid connection type 3W PE 3W N PE Efficiency Max efficiency 98 65 Euro eta 98 3 Specifications Model MID 6KTL3 XL MID 8KTL3 XL MID 10KTL3 XL MID 11KTL3 XL MID 12K...