background image

36

35

Don't disconnect the DC connector while the inverter is connected to the 
grid.

1.Close the inverter AC circuit breaker.
2.Close the DC switch, when the input PV voltage is higher than 250Vdc, and the inverter 
will start automatically.

12.1 Start the inverter

12.2 Shut down the inverter

Steps to turn off the inverter:

1. Disconnect the AC circuit breaker to prevent the inverter from starting again;

2. Turn off the DC switch;

3. Check the operating status of the inverter;

4. Wait until the LED and OLED display are off, indicating that the inverter is turned off.

Danger

12

 Start and shut down the inverter

Troubleshooting 

13

13.1 Error message

13.2 System error

When a malfunction occurs, an error message will be displayed on the OLED screen. 

Faults include system faults and inverter faults.

In some cases, you may be advised to contact Growatt, please provide the following 

information.
Information about the inverter:

Serial number

Model

Error message on OLED

A short description of the problem

Grid voltage

DC input voltage

Can you reproduce the failure? If so, how?

Has this problem occurred in the past?

What were the environmental conditions when the problem occurred?

Information about photovoltaic panels:

PV panel manufacturer's name and model

Panel output power

Voc of the panel

Vmp of the panel

Imp of the group

The number of panels in each string

If you need to replace the device, please ship it to the original box.

Warning Code

Warning

message

Description

Suggest

Warning 200 Panel access failure

1.Check  whether  the  panel  is  normal  after  shutting 

down;

2.If  the  fault  message  still  exists,contact  the 

manufacturer.

Warning 201 String/PID quick connect 

terminal abnormal

1.Check the string terminal wiring after shutdown;

2.If  the  fault  message  still  exists,  contact  the 

manufacturer.

Warning 202 DC  lightning  protection 

device alarm

1.Check the DC lightning arrester after shutdown;

2.If  the  fault  message  still  exists,contact  the 

manufacturer.

Warning 203 Panel short circuit

1.Check  whether  the  first  or  second  road  panel  or 

circuit is short-circuited;

2.If  the  fault  message  still  exists,  contact  the 

manufacturer.

Warning 204

Abnormal  function  of 

dry node

1.Check the dry node wiring after shutdown;

2.If  the  fault  message  still  exists,contact  the 

manufacturer.

Warning 205 Boost drive abnormal

1.Restart the inverter;

2.If  the  fault  message  still  exists,contact  the 

manufacturer.

Warning 206 AC  lightning  protection 

device alarm

1.Check the DC lightning arrester after shutdown;

2.If  the  fault  message  still  exists,  contact  the 

manufacturer.

11 

Maintenance and Cleaning 

11.1 Checking Heat Dissipation

11.2 Cleaning the Inverter

11.3 Checking the DC Disconnect

If  the  inverter  regularly  reduces  its  output  power  due  to  high  temperature,  please 

improve the heat dissipation condition. Maybe you need to clean the heat sink.

If the inverter is dirty, turn-off the AC breaker and DC switch ,waiting the inverter shut 

down ,then clean the enclosure lid, the display, and the LEDs using only a wet cloth. Do 

not use any cleaning agents (e.g. solvents or abrasives).

Check  for  externally  visible  damage  and  discoloration  of  the  DC  Disconnect  and  the 

cables at regular intervals.If there is any visible damage to the DC Disconnect, or visible 

discoloration or damage to the cables, contact the installer.

Ø

Once a year, turn the rotary switch of the DC Disconnect from the On position to the 

Off position 5 times in succession. This cleans the contacts of the rotary switch and 

prolongs the electrical endurance of the DC Disconnect.

Summary of Contents for MID 17KTL3-X1

Page 1: ...henzhen P R China No 28 Guangming Road Shiyan Street Bao an District Shenzhen P R China 86 755 2747 1942 www ginverter com www ginverter com T E W service ginverter com service ginverter com 86 755 27...

Page 2: ...cation of skilled person 2 3 Safety instruction 4 Unpacking inspection 5 Installation 5 1 Basic installation requirements 5 2 Mounting wall mount 5 3 Installing the inverter 6 1 Security 6 2 AC side w...

Page 3: ...nty 15 Decommissioning 17 Specification 16 EU declaration of conformity 18 EU declaration of conformity 9 1 Boot display 9 2 OLED display wake up 9 3 Function setting 12 1 Start the inverter 12 2 Shut...

Page 4: ...ted to the Growatt device or cause personal injury 1 3 2 Markings on this product CAUTION CAUTION indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE i...

Page 5: ...nverter and other communication products to communicate with each other The wireless communication device is not standard Require to order extral if you need it Safety 2 2 1 Product description and fe...

Page 6: ...e incorrect installation and operation may lead to serious safety and shock hazards and or equipment damage In order to minimize the possibility of shock hazards due to dangerous voltages cover the en...

Page 7: ...ugh charge to create a shock hazard In order to minimize the occurrence of this situation observe all corresponding safety symbols and marks in this manual Under special circumstances the inverter may...

Page 8: ...k whether the outer package is damaged After unpacking please check whether the appearance of the inverter is damaged or lack of accessories If there is damage or missing parts please contact the deal...

Page 9: ...y of the installation environment should be between 0 and 90 The ambient temperature around the inverter should be between 25 C 60 C The inverter can be mounted on a plane that is tilted vertically or...

Page 10: ...wall for power or other piping before opening the hole in the wall Danger Secure the wall mount as shown do not let the screws flush with the wall instead expose 2 to 4 mm 5 3 Installing the inverter...

Page 11: ...gle core wire at the output terminal of the inverter It is forbidden to use aluminum wires as output cables Please ensure that the output cable is well connected before turning on the inverter Ignorin...

Page 12: ...witch Measure the voltage and frequency of the public grid voltage AC 230V frequency 50Hz The recommended specifications of the AC output switch are as follows Inverter model Switch specification MID...

Page 13: ...utput terminal before turning it on otherwise the inverter will be damaged If a stable non zero DC voltage is measured between the positive pole of the photovoltaic string and the ground it means that...

Page 14: ...ive connector Negative metal terminal 4 6mm 4 6mm Fig 6 7 Fig 6 8 Fig 6 9 1 2 3 4 B just for Vietnam models B just for Vietnam models A A Fig 6 10 Fig 6 11 Fig 6 12 Fig 6 13 2 Push the threaded sleeve...

Page 15: ...In this case the company does not carry out warranty and assumes any responsibility Photovoltaic panel Inverter Distribution Cabinet SPD Power grid Lightning protection device Grounding bar 1 2 3 4 To...

Page 16: ...the disconnection device Do not generate power Do not generate at more than 50 of rated power Do not generate at more than 75 of rated power and reduce the reactive power as far as possible Increase...

Page 17: ...n permanent shutdown The inverter has large electrical potential differences between its conductors Arc flashes can occur through air when high voltage current flows Do not work on the product during...

Page 18: ...uency return to normal the inverter will automatically connect to the grid 8 2 Failure mode The inverter controls the chip monitors and adjusts the state of the system in real time When the inverter m...

Page 19: ...er than the domestic legal requirements the inverter cannot be connected to the grid After obtaining the permission of the local power operator the user can choose other voltage levels according to th...

Page 20: ...0 2 USB A The inverter side The inverter side The inverter side The inverter side Unistall up Install USB A port is mainly used to connect monitoring module or firmware update We can connect the exter...

Page 21: ...ct terminal abnormal 1 Check the string terminal wiring after shutdown 2 If the fault message still exists contact the manufacturer Warning 202 DC lightning protection device alarm 1 Check the DC ligh...

Page 22: ...manufacturer Warning 305 Reverse connection of current transformer 1 Check whether the current transformer is connected reversely 2 If the fault message still exists contact the manufacturer Warning 3...

Page 23: ...line 2 If the fault information still exists contact the manufacturer Error 308 Pairing timeout 1 The pairing of the machine and the current transformer is overtime re pair 2 If the fault information...

Page 24: ...ttery reverse connection protection tube 1 Restart the machine 2 If the fault information still exists ontact the manufacturer Error 424 Battery voltage sampling is inconsistent 1 Restart the machine...

Page 25: ...voltage 1100V Start voltage 250V Nominal voltage 600V MPP voltage range 200 1000V No of MPP trackers 3 No of PV strings per MPP trackers 2 2 2 2 2 2 2 2 2 2 2 2 Max input current per MPP trackers 26A...

Page 26: ...RS485 YES WIFI GPRS 4G RF LAN OPT Model Specifications MID 30KTL3 X MID 33KTL3 X MID 36KTL3 X MID 40KTL3 X Input data DC Max recommended PV power for module STC 45000W 49500W 54000W 60000W Max DC volt...

Page 27: ...5 YES WIFI GPRS 4G RF LAN OPT Model Specifications MID 17KTL3 X1 MID 20KTL3 X1 MID 22KTL3 X1 MID 25KTL3 X1 Input data DC Max recommended PV power for module STC 25500W 30000W 33000W 375000W Max DC vol...

Page 28: ...YES WIFI GPRS 4G RF LAN OPT Model Specifications MID 30KTL3 X MID 33KTL3 X MID 36KTL3 X MID 40KTL3 X Input data DC Max recommended PV power for module STC 45000W 49500W 54000W 60000W Max DC voltage 11...

Page 29: ...aces Display OLED LED USB RS485 YES WIFI GPRS 4G RF LAN OPT 17 2 Torque Shell cover screw 12kgf cm AC terminal block 14kgf cm AC waterproof cover fixing screw 4kgf cm Security screws on the wall mount...

Page 30: ...act the Growatt New Energy Service Hotline We need the following information to provide you with the necessary help Inverter type Inverter serial number Inverter error message code Inverter OLED displ...

Reviews: