13.3 System error

Error code

Description

Suggest

Error 200 DC arc abnormal

1.Check the panel terminal wiring after shutdown;
2.Restart the inverter;
3 . I f  t h e  f a u l t  m e s s a g e  s t i l l  e x i s t s , c o n t a c t  t h e 
manufacturer.

Error 201

Leakage  current  is 
too high

1.Restart the machine;
2.If  the  fault  information  still  exists,contact  the 
manufacturer.

Error 202

Panel  voltage  is 

too high

1.Disconnect the DC switch immediately and confirm the 

voltage;

2.After  the  normal  voltage  is  restored,if  the  fault 

message still exists,contact the manufacturer.

Error 203

Low panel

insulation

resistance

1.After  shutting  down,  check  whether  the  panel  shell  is 

reliably grounded;

2 . I f  t h e  f a u l t  m e s s a g e  s t i l l  e x i s t s , c o n t a c t  t h e 

manufacturer.

Error 300

The  mains  voltage 

is abnormal

1.Check the grid voltage;

2.If the grid voltage has recovered to the allowable range 

and  the  fault  information  still  exists,contact  the 

manufacturer.

Error 301 AC wiring error

1.Please check the mains terminal;

2 . I f  t h e  f a u l t  m e s s a g e  s t i l l  e x i s t s , c o n t a c t  t h e 

manufacturer.

Error 302

No mains

connection

1.Check the AC side line connection after shutdown;

2 . I f  t h e  f a u l t  m e s s a g e  s t i l l  e x i s t s , c o n t a c t  t h e 

manufacturer.

Error 303

Zero ground

detection anomaly

1.Check  the  ground  wire  after  shutting  down  to  ensure 

that the ground wire is connected reliably;

2 . I f  t h e  f a u l t  m e s s a g e  s t i l l  e x i s t s , c o n t a c t  t h e 

manufacturer.

Error 304 Abnormal mains

frequency

1.Detect grid frequency and restart;
2 . I f  t h e  f a u l t  m e s s a g e  s t i l l  e x i s t s , c o n t a c t  t h e 
manufacturer.

Error 305

Output  overload 
protection

1.Check output load, reduce load power;
2.If  the  fault  information  still  exists,contact  the 
manufacturer

Error 306

Reverse
connection of
current
transformer

1.Check  the  connection  direction  of  the  current 
transformer after shutdown;
2.If  the  fault  information  still  exists,contact  the 
manufacturer.

Error 307

Communication

failure  of  current 

transformer

1.Please check the communication line;

2.If  the  fault  information  still  exists,contact  the 

manufacturer.

Error 308 Pairing timeout

1.The pairing of the machine and the current transformer 
is overtime, re-pair;
2.If  the  fault  information  still  exists,contact  the 
manufacturer;

Error code

Description

Suggest

Error 400

Abnormal DC
component offset

1.Restart the machine;
2.If  the  fault  information  still  exists,contact  the 
manufacturer.

Error 401

The output
voltage DC
component  is  too 
high

1.Restart the machine;

2.If  the  fault  information  still  exists,contact  the 

manufacturer.

Error 402

The output

current DC

component  is  too 

high

1.Restart the machine;

2.If  the  fault  information  still  exists,contact  the 

manufacturer.

Error 403

Unbalanced

output current

1.Check  whether  the  output  current  is  unbalanced  after 

shutdown;

2.If  the  fault  message  still  exists,  contact  the 

manufacturer.

Error 404

Bus voltage

sampling is

abnormal

1 Restart the machine

2:  If  the  fault  information  still  exists,  contact  the 

manufacturer

Error 405 Relay abnormal

1.Restart the machine;
2.If  the  fault  information  still  exists,  contact  the 
manufacturer.

Error 406 Initialization

mode exception

1.Reset mode;

2 . I f  t h e  f a u l t  m e s s a g e  s t i l l  e x i s t s , c o n t a c t  t h e 

manufacturer.

Error 407

Automatic

detection failed

1.Restart the machine;
2.If  the  fault  information  still  exists,contact  the 
manufacturer.

Error 408

Temperature is too 

high

1.Check  the  temperature  after  shutdown,restart  the 
inverter after normal;
2 . I f  t h e  f a u l t  m e s s a g e  s t i l l  e x i s t s , c o n t a c t  t h e 
manufacturer.

Error 409

A b n o r m a l   b u s  

voltage

1.estart the machine;

2.If  the  fault  information  still  exists,  contact  the 

manufacturer.

Error 410

Inconsistent

insulation

resistance

sampling

1.Restart the machine;

2.If  the  fault  information  still  exists,contact  the 

manufacturer.

Error 411

Internal

communication
abnormal

1.Check  the  wiring  of  the  communication  version  after 
shutdown;
2.If  the  fault  message  still  exists,  contact  the 
manufacturer.

Error 412

Temperature

sensor  connection 

abnormal

1.Check  whether  the  temperature  sampling  module  is 

properly connected after shutdown;

2 . I f  t h e  f a u l t  m e s s a g e  s t i l l  e x i s t s , c o n t a c t  t h e 

manufacturer.

Summary of Contents for MID 17KTL3-X1

Page 1: ...henzhen P R China No 28 Guangming Road Shiyan Street Bao an District Shenzhen P R China 86 755 2747 1942 www ginverter com www ginverter com T E W service ginverter com service ginverter com 86 755 27...

Page 2: ...cation of skilled person 2 3 Safety instruction 4 Unpacking inspection 5 Installation 5 1 Basic installation requirements 5 2 Mounting wall mount 5 3 Installing the inverter 6 1 Security 6 2 AC side w...

Page 3: ...nty 15 Decommissioning 17 Specification 16 EU declaration of conformity 18 EU declaration of conformity 9 1 Boot display 9 2 OLED display wake up 9 3 Function setting 12 1 Start the inverter 12 2 Shut...

Page 4: ...ted to the Growatt device or cause personal injury 1 3 2 Markings on this product CAUTION CAUTION indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE i...

Page 5: ...nverter and other communication products to communicate with each other The wireless communication device is not standard Require to order extral if you need it Safety 2 2 1 Product description and fe...

Page 6: ...e incorrect installation and operation may lead to serious safety and shock hazards and or equipment damage In order to minimize the possibility of shock hazards due to dangerous voltages cover the en...

Page 7: ...ugh charge to create a shock hazard In order to minimize the occurrence of this situation observe all corresponding safety symbols and marks in this manual Under special circumstances the inverter may...

Page 8: ...k whether the outer package is damaged After unpacking please check whether the appearance of the inverter is damaged or lack of accessories If there is damage or missing parts please contact the deal...

Page 9: ...y of the installation environment should be between 0 and 90 The ambient temperature around the inverter should be between 25 C 60 C The inverter can be mounted on a plane that is tilted vertically or...

Page 10: ...wall for power or other piping before opening the hole in the wall Danger Secure the wall mount as shown do not let the screws flush with the wall instead expose 2 to 4 mm 5 3 Installing the inverter...

Page 11: ...gle core wire at the output terminal of the inverter It is forbidden to use aluminum wires as output cables Please ensure that the output cable is well connected before turning on the inverter Ignorin...

Page 12: ...witch Measure the voltage and frequency of the public grid voltage AC 230V frequency 50Hz The recommended specifications of the AC output switch are as follows Inverter model Switch specification MID...

Page 13: ...utput terminal before turning it on otherwise the inverter will be damaged If a stable non zero DC voltage is measured between the positive pole of the photovoltaic string and the ground it means that...

Page 14: ...ive connector Negative metal terminal 4 6mm 4 6mm Fig 6 7 Fig 6 8 Fig 6 9 1 2 3 4 B just for Vietnam models B just for Vietnam models A A Fig 6 10 Fig 6 11 Fig 6 12 Fig 6 13 2 Push the threaded sleeve...

Page 15: ...In this case the company does not carry out warranty and assumes any responsibility Photovoltaic panel Inverter Distribution Cabinet SPD Power grid Lightning protection device Grounding bar 1 2 3 4 To...

Page 16: ...the disconnection device Do not generate power Do not generate at more than 50 of rated power Do not generate at more than 75 of rated power and reduce the reactive power as far as possible Increase...

Page 17: ...n permanent shutdown The inverter has large electrical potential differences between its conductors Arc flashes can occur through air when high voltage current flows Do not work on the product during...

Page 18: ...uency return to normal the inverter will automatically connect to the grid 8 2 Failure mode The inverter controls the chip monitors and adjusts the state of the system in real time When the inverter m...

Page 19: ...er than the domestic legal requirements the inverter cannot be connected to the grid After obtaining the permission of the local power operator the user can choose other voltage levels according to th...

Page 20: ...0 2 USB A The inverter side The inverter side The inverter side The inverter side Unistall up Install USB A port is mainly used to connect monitoring module or firmware update We can connect the exter...

Page 21: ...ct terminal abnormal 1 Check the string terminal wiring after shutdown 2 If the fault message still exists contact the manufacturer Warning 202 DC lightning protection device alarm 1 Check the DC ligh...

Page 22: ...manufacturer Warning 305 Reverse connection of current transformer 1 Check whether the current transformer is connected reversely 2 If the fault message still exists contact the manufacturer Warning 3...

Page 23: ...line 2 If the fault information still exists contact the manufacturer Error 308 Pairing timeout 1 The pairing of the machine and the current transformer is overtime re pair 2 If the fault information...

Page 24: ...ttery reverse connection protection tube 1 Restart the machine 2 If the fault information still exists ontact the manufacturer Error 424 Battery voltage sampling is inconsistent 1 Restart the machine...

Page 25: ...voltage 1100V Start voltage 250V Nominal voltage 600V MPP voltage range 200 1000V No of MPP trackers 3 No of PV strings per MPP trackers 2 2 2 2 2 2 2 2 2 2 2 2 Max input current per MPP trackers 26A...

Page 26: ...RS485 YES WIFI GPRS 4G RF LAN OPT Model Specifications MID 30KTL3 X MID 33KTL3 X MID 36KTL3 X MID 40KTL3 X Input data DC Max recommended PV power for module STC 45000W 49500W 54000W 60000W Max DC volt...

Page 27: ...5 YES WIFI GPRS 4G RF LAN OPT Model Specifications MID 17KTL3 X1 MID 20KTL3 X1 MID 22KTL3 X1 MID 25KTL3 X1 Input data DC Max recommended PV power for module STC 25500W 30000W 33000W 375000W Max DC vol...

Page 28: ...YES WIFI GPRS 4G RF LAN OPT Model Specifications MID 30KTL3 X MID 33KTL3 X MID 36KTL3 X MID 40KTL3 X Input data DC Max recommended PV power for module STC 45000W 49500W 54000W 60000W Max DC voltage 11...

Page 29: ...aces Display OLED LED USB RS485 YES WIFI GPRS 4G RF LAN OPT 17 2 Torque Shell cover screw 12kgf cm AC terminal block 14kgf cm AC waterproof cover fixing screw 4kgf cm Security screws on the wall mount...

Page 30: ...act the Growatt New Energy Service Hotline We need the following information to provide you with the necessary help Inverter type Inverter serial number Inverter error message code Inverter OLED displ...

Reviews: