Under the permission given by your energy provider, the ratio of your system output
power divided by the rated power of the inverter is called Limit Rate.For instance,if the
energy provider only accepts 8kVA/kW from your 10kW system, then the Limit Rate of
10kW inverter is 80.0%.
Meter
CT
Set OK
Set parameter
General
Advanced
Password
***
Power Sensor
OFF
ON
If you only want to check the load consumption function,you can choose Meter as Power
sensor.CT is just only for Export Limit function.
7.3.3 Reset factory
Single touch to switch display or make the 1.
Double touch to confirm you setting.
Information
Perform this operation with caution because all configured parameters
except the current date,time, and model parameters will be restored to
their factory defaults.
Reset factory
NO
YES
Set OK
Set parameter
General
Advanced
Password
***
7.3.4 Adjust the setpoints from the regional default values
Under the permission by Distribution Network Service Provider,the installer can adjust
the setpoints from the regional default values.
Please refer to the document
《
Adjust the setpoints from the regional default values
instruction
》
7.4 Communications
7.4.1 RS485
This series inverter has one 4Pin or 16Pin signal socket .The inverter provides two RS485
ports. You can monitor one or more inverters by RS485.Another RS485 port is for smart
meter(Export limitation functionality.).
4Pin socket pin assignment
No.
Definition
1
2
3
4
RS485A1
RS 485B1
RS485A2
RS 485B2
communication
RS485 for
Smart Meter
Fig 7.1