9.3 Checking the DC Isolator
Check for externally visible damage and discoloration of the DC Isolator and the cables at
regular intervals.If there is any visible damage to the DC Isolator, or visible discoloration
or damage to the cables, contact the installer.
Ø
Once a year, turn the rotary switch of the DC Isolator from the On position to the Off
position 5 times in succession. This cleans the contacts of the rotary switch and
prolongs the electrical endurance of the DC Isolator.
10 EU Declaration of Conformity
With the scope of EU directives:
•2014/35/EU Low Voltage Directive (LVD)
•2014/30/EU Electromagnetic Compatibility Directive (EMC)
•2011/65/EU RoHS Directive and its amendment (EU)2015/863
Shenzhen Growatt New Energy Co. Ltd confirms that the Growatt inverters and
accessories described in this document are in compliance with the above mentioned
EU directives. The entire EU Declaration of Conformity can be found at www.ginverter.com.
11
Trouble shooting
Our quality control program assures that every inverter is manufactured to accurate
specifications and is thoroughly tested before leaving our factory. If you have difficulty in
the operation of your inverter, please read through the following information to correct
the problem.
11.1 Error Messages displayed on OLED
An error message will be displayed on the OLED screen when a fault occurs. The faults
consist of system fault and inverter fault.
You may be advised to contact Growatt in some situation, please provide the following
information.
Information concerning the inverter:
Serial number
Model number
Error message on OLED
Short description of the problem
Grid voltage
DC input voltage
Can you reproduce the failure? If yes, how?
Has this problem occurred in the past?
What was the ambient condition when the problem occurred?
Information concerning the PV panels:
Manufacturer name and model number of the PV panel
Output power of the panel
Voc of the panel
Vmp of the panel
Imp of the panel
Number of panels in each string
If it is necessary to replace the unit, please ship it in the original box.
11.2 System fault
System fault (system faults are mainly caused by system instead of inverter, please check
the items as instructed below before replacing inverter).
Error message
Description
Suggestion
AFCI fault
Error: 200
There is a high power
discharge of electricity
between two or more
conductors
1.After shut down the inverter,
check the connection of PV
terminals.
2.Restart the inverter.
3.If error message still exists,
contact Growatt.