6.4 Connecting the Battery
6.4.1
Conditions for the Battery
The MIN TL-XA single-phase inverter has one independent Battery input : BAT+/BAT-
connecting to the output of the Battery.
Notice that the connectors are in paired (male and female connectors). The connectors
for the Battery and inverters are Helios H4-R/VP-D4 connectors;
6.4.2 Connecting the Battery
DANGER
Danger to life due to lethal voltages!
Before connecting the Battery, ensure that it does not connect any
power supply. NEVER connect or disconnect the Battery.
Forbidden to reverse the positive and negative poles of the Battery and
the inverter.
Improper operation during the wiring process can cause fatal injury to
operator or unrecoverable damage to the inverter. Only qualified
personnel can perform the wiring work.
WARNING
WARNING
6.3 Connecting the second protective conductor
In some installation countries, a second protective conductor is required to prevent a
touch current in the event of a malfunction in the original protective conductor.For
installation countries falling within the scope of validity of the IEC standard 62109, you
must install the protective conductor on the AC terminal with a conductor cross-section
of at least 10 mm²Cu.Or Install a second protective conductor on the earth terminal with
the same cross-section as the original protective conductor on the AC terminal. This
prevents touch current if the original protective conductor fails.
Connection of BAT input terminal
4~6mm²
4~6mm²
Cable
Cable
Positive metal
terminal
Positive connector
Negative metal
terminal
Negative connector
Battery wiring panel