Commissioning
CAUTION
WARNING
DANGER
Do not disconnect the BAT connectors under load.
Improper operation during the wiring process can cause fatal injury to
operator or unrecoverable damage to the inverter. Only qualified
personnel can perform the wiring work.
Damage to the inverter due to moisture and dust penetration
Ø
Make sure the cable gland has been tightened firmly.
Ø
If the cable gland are not mounted properly, the inverter can be
destroyed due to moisture and dust penetration. All the warranty
claim will be invalid.
Requirements
:
ü
The AC cable is correctly connected.
ü
The BAT connectors are correctly connected.
ü
The country is set incorrectly.
7.1
Start the inverter
7.1.1 Touch control
Touch
Description
Single touch
Switch display or 1
Double touch
Enter or confirm
Three touch
Previous menu
Hold 5s
Confirm Country/Aera or recover defaut
value
7.1.2 Country setting Country/Area and Region setting
Information
Country setting
Ø
Before starts up the inverter,we need to select the right
Country/Area,if we don't select any Country/Area, the inverter will
run under AS/NZS4777.2 as default for Australia,or run under
VDE0126-1-1 for other region after 30s.
When inverter powered on, OLED will light automatically. Once the BAT power is
sufficient, OLED displays the following:
Press the touch key once a second to scroll through the different Country, showing on
the screen will constantly change.For example, if you want to choose Newzealand, press
the control key until the OLED display shows “Newzealand” as below:
Press the touch key 5S, the OLED shows Country setting is complete:
When the Country setting is complete, the OLED display shows “Set Region” as below:
We can set Region A,B or C when you choose Australia,but if you choose
Newzealand the default Region is NZ.
When Region A is selected, the inverter loads all the Region A values for power quality
response modes and grid protection settings.
7.1.3 Enabling/Disabling Power Quality Response Modes
(
PQRM
)
Information
PQRM setting
Ø
When the Region setting is completed, the inverter will operate
under default mode different from region.
MIN TL-XA contains five types Power Quality Response Modes
:
Volt-Var, Volt-watt, Fixed PF, Reactive power, Power limit.If you want to change the
Power Quality Response Modes please refer to chapter 7.3.1.
Growatt Inverter
Country/Area
XXXX
Single touch
Country /Area
Newzealand
Set OK
Growatt Inverter
Country /Area
Australia
Single touch
Country /Area
Australia
Single touch
Set Region
A B C
Default Region
NZ