Trouble shooting
Our quality control program assures that every inverter is manufactured to accurate
specifications and is thoroughly tested before leaving our factory. If you have difficulty in
the operation of your inverter, please read through the following information to correct
the problem.
11.1 Error Messages displayed on OLED
An error message will be displayed on the OLED screen when a fault occurs. The faults
consist of system fault and inverter fault.
You may be advised to contact Growatt in some situation, please provide the following
information.
Ÿ
Serial number
Ÿ
Model number
Ÿ
Error message on OLED
Ÿ
Short description of the problem
Ÿ
Grid voltage
Ÿ
Can you reproduce the failure? If yes, how?
Ÿ
Has this problem occurred in the past?
Ÿ
What was the ambient condition when the problem occurred?
Information concerning the inverter:
11.2 System fault
System fault (system faults are mainly caused by system instead of inverter, please check
the items as instructed below before replacing inverter).
Error message
Description
Suggestion
Residual I High
Error: 201
Leakage current too high
Restart the invert.
If error message still exists, contact
Growatt.
AC V Outrange
Error: 300
Utility grid voltage is out
of permissible range.
1.Please switch off DC switch.
2.Check AC wiring, especially neutral
and ground wire.
3.Check grid voltage is complied with
local grid standard. Restart inverter, if
problem still exist, 4.Contact Growatt.
No AC connection
Error: 302
No AC connection
Check AC wiring.
Check the status of AC breaker
PE abnormal Error:
303
Voltage of Neutral and PE
above 30V.
Check the voltage of Neutral and PE.
Check AC wiring.
Restart inverter, if error message still
exisits,contact Manufacturer
AC F Outrange
Error: 304
Utility grid frequency out
of permissible range.
1.Please switch off DC switch.
2.Check AC wiring, especially neutral
and ground wire.
3.Check grid frequency is complied
with local grid standard.
4.Restart inverter, if problem still exist,
Contact Growatt.
Auto Test Failed
Error: 407
Auto test didn't pass.
1.Restart inverter, repeat Auto Test, if
problem still exist, contact Growatt.
11.3 Inverter warning
Warning code
Meanings
Suggestion
Warning 204
Dryconnect function
abnormal
1.After shutdown,Check the dry
Dryconnect wiring.
2.If the error message still exists,
contact manufacturer.
Warning 207
USB over-current
1.Unplug the U disk or monitor.
2.Re-access U disk or monitor after
shutdown.
3.If the error message still exists,
contact manufacturer.