Electrical connection
Decisive Voltage Class (DVC) indicated for ports
Port Name
Class
AC Output
C
DC Input
C
COM&SYS COM Port
A
RS485&USB
A
6.1
Safety
Danger to life due to lethal voltages!
High voltages which may cause electric shocks are present in the
conductive parts of the inverter. Prior to performing any work on the
inverter, disconnect the inverter on the AC and DC sides
WARNING
Danger of damage to electronic components due to electrostatic
discharge.
Take appropriate ESD precautions when replacing and installing the
inverter.
6.2
Wiring AC Output
WARNING
You must install a separate single-phase circuit-breaker or other
load disconnection unit for each inverter in order to ensure that
the inverter can be safely disconnected under load.
NOTE :
The inverter has the function of detecting residual current and protecting
the inverter against residual current.
If an external RCD breaker is
mandatory in the country of installation,you must choose a Type A RCD
breaker with the rating residual current not less than 300mA.
You must install a separate single-phase circuit-breaker or other load disconnection unit for
each inverter in order to ensure that the inverter can be safely disconnected under load.
We suggest you choice the AC breaker rating current in this table:
The AC wiring step:
1.
Uninstall the parts of the AC connection plug from the accessory bag.
2.
Insert the stripped and bared cable through pressure screw, seal ring, threaded sleeve
in sequence, insert cables into connection terminal according to polarities indicates on
it and tighten the screws firmly. Please try to pull out the wire to make sure the
it’s well
connected.
MIN 2500TL-XH
16A/230V
MIN 3000TL-XH
16A/230V
MIN 3600TL-XH
20A/230V
MIN 4200TL-XH
25A/230V
MIN 4600TL-XH
25A/230V
MIN 5000TL-XH
32A/230V
MIN 6000TL-XH
32A/230V