20
19
5.
To remove the AC connector, press the bayonet out of the slot with a small
screwdriver and pull it out,or unscrew the threaded sleeve,then pull it out.
Wire suggestion length
Conductor cross
section
Max. cable length
MIN 2500 TL-XH
MIN 3000 TL-XH
MIN 3600 TL-XH
4 mm² 12AWG
48m
40m
33m
5.2 mm² 10AWG
60m
50m
42m
Conductor cross
section
Max. cable length
MIN 4200 TL-XH
MIN 4600 TL-XH
MIN 5000 TL-XH
MIN 6000 TL-XH
5.2 mm² 10AWG
28m
26m
24m