Commissioning
DANGER
Do not disconnect the PV&BAT connectors under load.
WARNING
Improper operation during the wiring process can cause fatal injury to
operator or unrecoverable damage to the inverter. Only qualified
personnel can perform the wiring work.
CAUTION
Damage to the inverter due to moisture and dust penetration
Make sure the cable gland has been tightened firmly.
If the cable gland are not mounted properly, the inverter can be
destroyed due to moisture and dust penetration. All the warranty
claim will be invalid.
Requirements
:
The AC cable is correctly connected.
The PV&BAT connectors are correctly connected.
The country is set incorrectly.
7.1
Start the inverter
7.1.1
Touch control
Touch
Description
Single touch
Switch display or 1
Double touch
Enter or confirm
Three touch
Previous menu
Hold 5s
Confirm Country/Aera or recover
defaut value
7.1.2
Country setting Country/Area and Region setting
Information
Country/Area and Region setting
When the inverter start up,we need to select the right country,if
we don’t select any country, the inverter will run under
AS/NZS4777.2 as default for Australia & Region A,or run under
VDE0126-1-1 for other region after 30s.
When inverter powered on, OLED will light automatically. Once the PV power is sufficient, OLED displays
the following:
Growatt
PV inverter
Country/Aera
XXXX
Press the touch key once a second to scroll through the different Country, showing on the screen will
constantly change.For example, if you want to choose Newzealand, press the control key until the OLED
display shows “Newzealand” as below:
Country/Aera
Newzealand
Press the touch key 5S, the OLED shows Country setting is complete.
Set OK
When the Country setting is complete, the OLED
display shows “Set Region” as below:
Growatt
PV inverter
Country/Aera
Australia
Country/Aera
New Zealand
Set Region
A B C
Default Region
NZ
We can set Region A,B or C when you choose Australia,but if you choose
Newzealand the default Region is NZ.
When Region A is selected, the inverter loads all the Region A values for power quality response modes
and grid protection settings.
7.1.3
Enabling/Disabling Power Quality Response Modes
(
PQRM
)
Information
PQRM setting
When the Region setting is completed, the inverter will operate under
default mode different from region.
MIN TL-XH contains five types Power Quality Response Modes
:
Volt-Var, Volt-watt, Fixed PF, Reactive power, Power limit.If you want to change the
Power Quality Response Modes please refer to chapter 7.3.1.