background image

6

 

5

 

 

 

2.3

 

Safety instruction 

The  MIN  TL-XH  Inverters  is  designed  and  tested  according  to  international  safety 
requirements

( 

IEC62109-1,CE,VDE-AR-N4105,CEI0-21,VDE0126-1-1, AS4777,ect.

) 

;

 

however, certain safety precautions must be observed when installing and  operating

 

this  inverter.  Read  and  follow  all  instructions,  cautions  and  warnings  in  this  installation 
manual.  If  questions  arise,  please  contact  Growatt's  technical  services  at  +86  (0)755  2747 
1942.

 

 

2.4

 

Assembly Warnings 

 

 
 

 

 

WARNING

 

 

Prior to installation, inspect the unit to ensure absence of any 
transport or handling damage, which could affect insulation 
integrity or safety clearances; failure to do so could result in safety 
hazards.

 

 

Assemble the inverter per the instructions in this manual. Use care 
when choosing installation location and adhere to specified 
cooling requirements.

 

 

Unauthorized removal of necessary protections, improper use, 
incorrect installation and operation may lead to serious safety and 
shock hazards and/or equipment damage.

 

 

In order to minimize the potential of a shock hazard due to 
hazardous voltages, cover the entire solar array with dark material 
prior to connecting the array to any equipment.

 

 

 

 

CAUTION

 

 

Grounding the PV modules

: 

The MIN TL-XH is a transformerless 

inverter. That is why it has no galvanic separation. Do not ground 
the  DC circuits  of the  PV modules  connected  to  the  MIN TL-XH. 
Only  ground  the  mounting  frame  of  the  PV  modules.If  you 
connect  grounded  PV  modules  to  the  MIN  TL-XH,  the  error 
message "PV ISO Low".

 

Comply  with  the  local  requirements  for  grounding  the  PV 
modules  and  the  PV  generator.  GROW ATT  rec ommends 
connecting the generator frame and other electrically conductive 
surfaces in a manner  which ensures  continuous conduction  with 
ground  in  order  to  have  optimal  protection  of  the  system  and 
personnel.

 

2.5

 

Electrical Connection Warnings 

 

 

 

Persons with limited physical or mental abilities may only work 
with the Growatt inverter following proper instruction and under 
constant supervision. Children are forbidden to play with the 
Growatt inverter. Must keep the Growatt inverter away from 
children.

 

 

 

WARNING

 

 

Make all electrical connections (e.g. conductor termination, 
fuses, PE connection, etc.) in accordance with prevailing 
regulations. When working with the inverter powered on, adhere 
to all prevailing safety regulations to minimize risk of accidents.

 

 

Systems with inverters typically require additional control (e.g., 
switches, disconnects) or protective devices (e.g., fusing circuit 
breakers) depending upon the prevailing safety rules.

 

 

2.6

 

Operation Warnings 

 

 
 
 

 

 

DANGER

 

 

The components in the inverter are live. Touching live components 
can result in serious injury or death.

 

 

Do not open the inverter except the wire box by qualified persons.

 

 

Electrical installation, repairs and conversions may only be carried 
out by electrically qualified persons.

 

 

Do not touch damaged inverters.

 

 

Danger to life due to high voltages in the inverter

 

 

There is residual voltage in the inverter. The inverter takes 20 
minutes to discharge.

 

 
 

 

 

 

Ensure all connectors are sealed and secure during operation.

 

Although designed  to meet all safety requirements, some parts 
and surfaces of Inverter are still hot during operation. To reduce 
the  risk  of  injury,  do  not  touch  the  heat  sink  at  the  back  of  the 
Inverter or nearby surfaces while Inverter is operating.

 

Incorrect  sizing  of  the  PV  plant  may  result  in  voltages  being 
present which could destroy the inverter. The inverter display will 

 

 

 

 

 

 

Turn  the  rotary  switch  of  the  DC  Disconnect  to  the  Off  position 

immediately.

 

Contact installer.

 

 
 
 
 

 

 

 

All operations regarding transport, installation and start-up, 
including maintenance must be operated by qualified, trained 
personnel and in compliance with all prevailing codes and 
regulations.

 

Anytime the inverter has been disconnected from the power 
network, use extreme caution as some components can retain 
charge sufficient to create a shock hazard; to minimize 
occurrence of such conditions, comply with all corresponding 
safety symbols and markings present on the unit and in this 
manual.

 

In special cases, there may still be interference for the specified 
application area despite maintaining standardized emission limit 
values (e.g. when sensitive equipment is located at the setup 
location or when the setup location is near radio or television 
receivers).In this case, the operator is obliged to take proper 
action to rectify the situation.

 

Do not stay closer than 20 cm to the inverter for any length of 
time.

 

 

Summary of Contents for MIN 2500TL-XH

Page 1: ...MIN 6000TL XH Download Manual Installation Operation Manual Growatt New Energy CO LTD 4 13 F Building A Sino German Europe Industrial Park Hangcheng Ave Bao an District Shenzhen P R China T 86 0755 27...

Page 2: ...ngs TL XH overview Type label Size and weight Storage of inverter The advantage of theunit Validity Target group Additional information Symbols in this document Glossary Safety instructions Selecting...

Page 3: ...erter Specification PV BAT AC connectors info Torque Accessories Start the inverter General setting Advanced setting Communication interfaces Startup the inverter Shutdown the inverter Checking heat d...

Page 4: ...sponsibilities to inform the users 1 4 Symbols in this document 1 4 1 Warings in this document A warning describes a hazard to equipment or personnel It calls attention to a procedure or practice whic...

Page 5: ...XH MIN 4200TL XH MIN 4600TL XH MIN 5000TL XH MIN 6000TL XH inverters are built according to all required safety rules Nevertheless improper use may cause lethal hazards for the operator or third part...

Page 6: ...onnections e g conductor termination fuses PE connection etc in accordance with prevailing regulations When working with the inverter powered on adhere to all prevailing safety regulations to minimize...

Page 7: ...r 3 2 Type label The type labels provide a unique identification of the inverter The type of product Device specific characteristics Certificates and approvals The type labels are on the left hand sid...

Page 8: ...al package and should be stored in a clean and dry place and be protected from dust and water vapor corrosion The storage temperature should be always between 25 and 60 And the storage relative humidi...

Page 9: ...olutely necessary Growatt assumes no responsibility for compliance to EMC regulations for the complete system All electrical installations shall be done in accordance with the local and national elect...

Page 10: ...horizontal and avoids forward and sideways tilt Be sure that the inverter is out of the children s reach Don t put any things on the inverter Do not cover the inverter Do not install the inverter near...

Page 11: ...ed the inverter on the wall WARNING Falling equipment can cause serious or even fatal injury never mount the inverter on the bracket unless you are sure that the mounting frame is really firmly mounte...

Page 12: ...sidual current and protecting the inverter against residual current If an external RCD breaker is mandatory in the country of installation you must choose a Type A RCD breaker with the rating residual...

Page 13: ...20 19 3 Push the threaded sleeve into the socket Tighten up the cap on the terminal 4 Finally Push or screw the threaded sleeve to connection terminal until both are locked tightly on the inverter...

Page 14: ...the threaded sleeve then pull it out Wire suggestion length Conductor cross section Max cable length MIN 2500 TL XH MIN 3000 TL XH MIN 3600 TL XH 4 mm 12AWG 48m 40m 33m 5 2 mm 10AWG 60m 50m 42m Condu...

Page 15: ...in paired male and female connectors The connectors for PV arrays and inverters are Helios H4 R VP D4 connectors Types Max current PV1 Max current PV2 Max voltage 2500 3000 TL XH 13 5A 13 5A 500V 3600...

Page 16: ...rator or unrecoverable damage to the inverter Only qualified personnel can perform the wiring work Connection of BAT input terminal 4 6mm Cable Positive metal terminal Positive connector 6 5 Connectin...

Page 17: ...6 AntiReFlux_B Connect meter signal RS485B 7 BAT_B Connect Battery communication RS485B or CANL 8 BAT_A Connect Battery communication RS485A or CANH CAUTION The communication interface RS485 or CAN be...

Page 18: ...n is used to control the active or apparent power output levels of an inverter The export limit control function for an inverter is used to control the generation from an inverter to manage the export...

Page 19: ...to inverter Meter Pin NO Description Meter Connection 1 CT input CT P White 2 CT N Black or Blue 3 N in Grid N 4 L in Grid L 9 RS485B RS485B2 connect to inverter SYS COM Pin 8 10 RS485A RS485A2 conne...

Page 20: ...DRM8 are available CAUTION Damage to the inverter due to moisture and dust penetration Make sure the cable gland has been tightened firmly If the cable gland are not mounted properly the inverter can...

Page 21: ...on t over 5V RRCR PCI Connector 6 9 2 1 The connector pin assignment and function definition Pin Assignment for inverters capable of both charging and discharging 12V GND DRM 1 5 DRM 2 6 DRM 3 7 DRM 4...

Page 22: ...with a power of 300 W or greater must be interrupted by the AFCI within the time specified by UL 1699B A tripped AFCI can only be reset manually You can deactivate the automatic arc fault detection a...

Page 23: ...n under VDE0126 1 1 for other region after 30s When inverter powered on OLED will light automatically Once the PV power is sufficient OLED displays the following Growatt PV inverter Country Aera XXXX...

Page 24: ...o switch display Double touch to enter next stage menu Grid XXXvXXXHz Etotal XXXXw Etoday XXXkWh Power XXXXw Model S03B00D 00T00P00U00M0 000 FW Ver AK X X More Info Set parameter PV2 XXXvXXXXw PV1 XXX...

Page 25: ...ing Set inverter date as described below 7 2 3 Set inverter date Single touch make the number up Double touch to confirm the setting Set inverter date as described below 7 2 4 Set inverter time Single...

Page 26: ...ry Aera xxxxxxx Set OK Set parameter General Advanced Password Reset Region Set Region A B C NO YES Set OK Set parameter General Advanced Password Reset PQRM Set PQRM Volt Var Set PQRM xxxxxxx Set OK...

Page 27: ...s three working modes Grid priority Battery priority and Load priority default is Load priority mode Users can set the inverter to work in different modes in different time periods through OLED Single...

Page 28: ...ime3 Disable Multiple single Single touch Double touch touch LoadFirst NN 01 touch LoadFirst 00 NN touch 7 4 2 COM Port BatFirst 00 01 Time3 Disable Time3 Disable Time3 Disable The XH series inverter...

Page 29: ...ts output power due to high temperature please improve the heat dissipation condition Maybe you need to clean the heat sink 9 2 Cleaning the Inverter If the inverter is dirty turn off the AC breaker D...

Page 30: ...nverter please read through the following information to correct the problem 11 1 Error Messages displayed on OLED An error message will be displayed on the OLED screen when a fault occurs The faults...

Page 31: ...k AC wiring especially neutral and ground wire 3 C h e c k g r i d f r e q u e n c y i s complied with local grid standard 4 Restart inverter if problem still exist Contact Growatt Auto Test Failed Er...

Page 32: ...or electronic waste which apply at the installation site at that time Ensure that the old unit and where applicable any accessories are disposed of in a proper manner Wait 20 minutes before disassembl...

Page 33: ...2500VA 3000VA 3600VA 4200VA Nominal AC voltage 230V AC voltage range 160 276V Norminal AC grid frequency 50 60Hz AC grid frequency range 45 55Hz 55 65Hz Rated output current 10 9A 13A 15 7A 18 3A Max...

Page 34: ...tage 100V Min operating voltage 70V Nominal voltage 360V PV input operating voltage range 70 550V MPP voltage range at Full Power 180V 500V 190V 500V 230V 500V No of MPP trackers No of PV strings per...

Page 35: ...y range 45 55Hz 55 65Hz Max efficiency 98 4 98 4 98 4 Euro eta 97 5 97 5 97 5 DC reverse polarity protection Integrated DC switch Integrated DC Surge protection class Insulation resistance monitoring...

Page 36: ...t device of equivalent value according to model and age The warranty shall not cover transportation costs in connection with the return of defective modules The cost of the installation or reinstallat...

Reviews: