6 Battery Life Maintenance
(Important)
a) TUnplug Battery power, Battery Communication cables and turn OFF battery modules
power (Check battery quick installation guide for the detail) .
if the following conditions were met:
Ø
The installation is not completed.
Ø
No PV and AC power can charge the battery.
b) Charge the battery SOC above 60% or higher after installation is complete and
pending for AHJ/city review and approval.
Commissioning Error Code 7
Troubleshooting
Enter the local commissioning home page, and view the fault and alarm information on
the main interface if there are exist after installation. The fault and alarm code on the
ShineServer Page will be the same in the APP.
If you find a fault or alarm, please click it, and then you will be redirected to the interface
of fault explanation and handling tips.
1. Common Fault and warning Codes
Fault code
Fault name
Possible cause
suggestion
Error 200
AFCI Fault
There is a problem on
the wiring connection
1.After shutdown, check the
panel terminal.
2.Decrease AFCI sensitivity
and restart.
3.If error message still exists,
contact manufacturer.
Error 201
Residual current
High
PV panel insulation
problem
1.Restart inverter. (Related
to Grounding fault?)
2.If error message still exists,
contact manufacturer.
18
17