6.5 AC connection
6.5.1 Connecting the AC output power cable for AC Grid
6.5.2 Connecting the AC output power cable for BACKUP
6.5.3 ATS-US connection
Strip 0.7 inches (18mm) of the AC cable insulation.
Insert the AC conduit into the AC-side drill guide that was opened
Insert the 0.8*4.0 mm standard flat-blade screwdriver and press the release
mechanism and open the clamp
Connect the cable to the appropriate terminal blocks according to the labels on the
terminal blocks(L1,N,L2,of AC Grid)
Insert the cable into the round opening and remove the screwdriver, then the cable is
automatically clamped
Connect the PE to the Grounding terminal
Keep the wiring box clean
Strip 0.7 inches (18mm) of the AC cable insulation.
Insert the AC conduit into the AC-side drill guide that was opened
Insert the 0.8*4.0 mm standard flat-blade screwdriver and press the release
mechanism and open the clamp
Connect the cable to the appropriate terminal blocks according to the labels on the
terminal blocks(L1,L2,of Backup)
Insert the cable into the round opening and remove the screwdriver, then the cable is
automatically clamped
Connect the PE to the Grounding terminal
Keep the wiring box clean
Fig 6.12
Fig 6.13
Open the ATS cover
Remove the hole tapes for installing conduit
Insert AC backup conduit
Insert the 0.8*4.0 mm standard flat-blade screwdriver and press the release
mechanism and open the clamp
Connect the cable to the appropriate terminal blocks according to the labels on the
terminal blocks (L1, L2, of Backup)
Insert the cable into the round opening and remove the screwdriver, then the cable is
automatically clamped
Connect the PE to the Grounding terminal
Keep the ATS-US box clean
Cables connecting between the ATS-US and MIN TL-XH US inverter
ATS-US
Inverter
Type
Conductor cross-
sectional area range
L1(EPS input)
L1(backup)
solid or stranded
wire but not fine
stranded wire
12-4 AWG
L2(EPS input)
L2(backup)
The ATS-US is used for backup storage function.
Before the ATS-US connection need to install a secondary AC panel for
backup loads. Rewire the backup loads through this panel.
Cables connecting between the ATS-US and AC panel refers to ATS-US
installation manual.
27
28
NOTICE