5.2.4 AC Couple Setting
1.Tap in Quick Setting icon
2.Find Enable AC Couple
3.Tap in ON/OFF button
The AC Couple setting is what the AC COUPLE system needs to set
Factory Default is Disabled.
15
16
5.2.5 MIN TL-XH-US Inverter communication setting with SYN 200-XH-US
1.Tap in System
Configuration
2.Tap in Off-Grid Function
3.Tap in Enable Off-Grid
Function button
MIN TL-XH-US inverter with SYN 200-XH-US needs to set the off-grid and electric meter
enable
Factory Default is disable.Off-Grid enable settings are as follows,please refer to
chapter 5.2.1 for meter settings
1.Tap in EMS
2.Tap in Time Slot…
3.Create the date and time
period.
5.2.6 EMS Mode Setting:
If an ARO battery is installed in the system, you need to set the energy storage mode.
Factory Default is Maximum Self-Consumption.
Example:
If the energy storage system is to be used as backup and only use the battery
when the grid is powered off, set the battery charging and discharging time period to 24
hours for TOU Battery Charging.