5 Installation
5.1
Basic installation requirements
>
The wall on which the inverter is mounted must be sturdy and can withstand the weight of
the inverter for a long time (refer to the specifications in Chapter 17 for the weight of the in-
verter);
>
The installation location must match the size of the inverter;
>
Do not install the inverter on a building constructed of flammable or heat-resistant mate-
rials;
>
Install the inverter in an eye-view orientation to facilitate inspection of the OLED display
and maintenance work;
>
The machine's degree of protection is IP66 and can be installed indoors and outdoors;
>
It is not recommended to expose the inverter directly to strong sunlight to prevent over-
heating and cause power derating;
>
The humidity of the installation environment should be between 0 and 90%;
>
The ambient temperature around the inverter should be between -25 ° C ~ 60 ° C;
>
The inverter can be mounted on a plane that is tilted vertically or backwards.
Please refer to the following figure:
Fig 5.1 Installation diagram
>
In order to ensure the normal operation of the machine and the convenience of personnel
operation, please pay attention to provide sufficient clearance for the inverter. Please refer to
the figure below:
Direction
Minimum clearance (mm)
Above
500
Under
500
Both sides
300
Forward
300
11
Summary of Contents for MOD 1 0KTL3-X
Page 1: ...Asennus ja k ytt ohje...
Page 19: ...Kuva 5 9 Kaaviokuva invertterin sein asennuksesta 15...
Page 60: ...Installations och bruksanvisning...
Page 78: ...Figur 5 9 Schema f r v ggmontering av v xelriktaren 15...
Page 119: ...Kontaktuppgifter 19 Suomi Trading Oy Areenakatu 7 37570 Lemp l asiakaspalvelu suomitrading fi...
Page 120: ...Installation Operation Manual...
Page 138: ...Fig 5 9 Schematic diagram of inverter wall mounting 15...
Page 179: ...Contact us 19 Suomi Trading Oy Areenakatu 7 37570 Lemp l asiakaspalvelu suomitrading fi 56...
Page 180: ......