6.8
Inverter demand response modes (DRMS)
This series inverter has the function of demand response modes, We use 16-Pin socket as in-
verter DRMS connection.
6.8.1 16-Pin socket pin assignment
Pin No.
Assignment for inverters capable of both charging and discharging
9
DRM 5
10
DRM 6
11
DRM 7
12
DRM 8
13
RefGen
14
Com/DRMO
15
NC
16
NC
6.8.2 Method of asserting demand response modes
Mode Socket asserted by
shorting pins
Function
DRM 0
14
13
Operate the disconnection device.
DRM 5
9
13
Do not generate power.
DRM 6
10
13
Do not generate at more than 50% of rated power.
DRM 7
11
13
Do not generate at more than 75% of rated power and re-
duce the reactive power as far as possible.
DRM 8
12
13
Increase power generation (subject to constraints from other
active DRMs).
27
DRMS application description
>
Applicable to AS/NZS4777.2:2015 or Commission Regulation (EU)
2016/631.
>
DRMO, DRM5, DRM6, DRM7, DRM8 are available.
Damage to the inverter due to moisture and dust penetration
>
Make sure the cable gland has been tightened firmly.
>
If the cable gland are not mounted properly, the inverter can be de-
stroyed due to moisture and dust penetration. All the warranty claim
will be invalid.
Excessive voltage can damage the inverter! Exter-
nal voltage of DRM PORT don't over +5V.
Information
CAUTION
W A R N I N G
Summary of Contents for MOD 1 0KTL3-X
Page 1: ...Asennus ja k ytt ohje...
Page 19: ...Kuva 5 9 Kaaviokuva invertterin sein asennuksesta 15...
Page 60: ...Installations och bruksanvisning...
Page 78: ...Figur 5 9 Schema f r v ggmontering av v xelriktaren 15...
Page 119: ...Kontaktuppgifter 19 Suomi Trading Oy Areenakatu 7 37570 Lemp l asiakaspalvelu suomitrading fi...
Page 120: ...Installation Operation Manual...
Page 138: ...Fig 5 9 Schematic diagram of inverter wall mounting 15...
Page 179: ...Contact us 19 Suomi Trading Oy Areenakatu 7 37570 Lemp l asiakaspalvelu suomitrading fi 56...
Page 180: ......