13.3
System error
Error code
Description
Suggest
Error 200 AFCI Fault
1 .After shutdown,Check the panel terminal.
2.Restart inverter.
3.If error message still exists,contact manufacturer.
Error 201 L e a k a g e cu r -
r e n t too high.
1 .Restart inverter.
2.If error message still exists,contact manufacturer.
Error 202
The DC input volt-
age is exceeding
the maximum toler-
able value.
1 .Immediately disconnect the DC switch and check the volt-
age
2.If the fault code still exists after the normal voltage is re-
stored, contact manufacturer
Error 203 PV isolation Low
1.After shutdown, check whether the panel shell is reliably
grounded.
2.If error message still exists,contact manufacturer.
Error 300 AC V Outrange
1 .Check grid voltage.
2.If the error message still exists despite the grid voltage be-
ing within the tolerable range, contact manufacturer.
Error 301 AC t e r m i n a l s re-
versed
1 .Check AC terminals
2.If error message still exists,contact manufacturer.
Error 302 No AC Connection
1 .After shutdown,Check AC wiring.
2.If error message still exists,contact manufacturer.
Error 303 NE abnormal
1 .Check PE,to ensure that the PE line contact good. 2.If error
message still exisits,contact Manufacturer.
Error 304 AC F Outrange
1 .Restart inverter.
2.If error message still exists,contact manufacturer.
Error 305 Over Load Fault
1.Check whether output load over range; If load too large,
please reduce load
2.If error message still exists, contact manufacturer.
Error 306 CT LN Reversed
1 .After shutdown Check the SP-CT connection.
2.If error message still exists,contact manufacturer.
Error 307
C o m m u n i ca t i o n
fault M3 didn't re-
ceive SP-CT data
1 .Check communication wire
2.If error message still exists,contact manufacturer.
Error 308
C o m m u n i ca t i o n
fault;Pairing
time
too long
1 .Restart pairing
2.If error message still exists,contact manufacturer.
41
Summary of Contents for MOD 1 0KTL3-X
Page 1: ...Asennus ja k ytt ohje...
Page 19: ...Kuva 5 9 Kaaviokuva invertterin sein asennuksesta 15...
Page 60: ...Installations och bruksanvisning...
Page 78: ...Figur 5 9 Schema f r v ggmontering av v xelriktaren 15...
Page 119: ...Kontaktuppgifter 19 Suomi Trading Oy Areenakatu 7 37570 Lemp l asiakaspalvelu suomitrading fi...
Page 120: ...Installation Operation Manual...
Page 138: ...Fig 5 9 Schematic diagram of inverter wall mounting 15...
Page 179: ...Contact us 19 Suomi Trading Oy Areenakatu 7 37570 Lemp l asiakaspalvelu suomitrading fi 56...
Page 180: ......