18
Preparation before wiring
:
Connect the protective ground wire (PE)
Connect
the
inverter
to
the
grounding
bar
through
the
protective
earth (PE)
to
achieve
grounding
protection.
Ø
Good
grounding
is
good
for
resisting
surge
voltage
impact
and
improving
EMI
performance
.
Therefore,you
need
to
ground
the
wire
before
connecting
the
AC,DC,and
communication
cables
.
Ø
For
a
single
-
machine
system,only
the
PE
cable
needs
to
be
grounded;For
a
multi
-
machine
system,the
PE
cables
of
all
inverters
need
to
be
connected
to
the
same
grounding
copper
bar
to
ensure
equipotential
connection
.
Ø
Disconnect
the
inverter
DC
switch,AC
side
circuit
breaker
or
switch
.
Ø
Measure the voltage and frequency of the public grid (voltage:AC 230V;
frequency:50Hz)
Ø
The
recommended
specifications
of
the
AC
output
switch
are
as
follows:
Inverter model
Switch specification
Inverter model
Switch specification
MOD 3000TL3-X
10A/230V
MOD 9000TL3-X-AU
20A/230V
MOD 4000TL3-X
10A/230V
MOD 10KTL3-X
25A/230V
MOD 5000TL3-X
15A/230V
MOD 10KTL3-X-AU
25A/230V
MOD 6000TL3-X
15A/230V
MOD 11KTL3-X
25A/230V
MOD 7000TL3-X
15A/230V
MOD 11KTL3-X-AU
25A/230V
MOD 7000TL3-X-AU
15A/230V
MOD 12KTL3-X
25A/230V
MOD 8000TL3-X
20A/230V
MOD 13KTL3-X
30A/230V
MOD 8000TL3-X-AU
20A/230V
MOD 15KTL3-X
30A/230V
MOD 9000TL3-X
20A/230V
/
/
17
Fig 6.1 Grounding
diagram
AC connection steps:
1.Pass the 5 wires (A,B,C,N and PE wires) through the AC shield,connect them to the
power grid,and then crimp the O/U terminal.
2. Lock the AC cable to the corresponding AC terminal.
3.Lock the protective cover on the inverter frame, and finally tighten the protective cover
hole.
Fig 6.4 AC quick connection diagram
Fig 6.3 Wiring diagram of AC terminal
Fig 6.2 AC output wiring diagram