Preparation before wiring :
Connect the protective ground wire (PE)
Connect the inverter to the grounding bar through the protective earth (PE) to achieve grounding
protection.
Fig 6.1 Grounding diagram
>
Disconnect the inverter DC switch,AC side circuit breaker or switch.
>
Measure the voltage and frequency of the public grid (voltage:AC 230V;
frequency:50Hz)
>
The recommended specifications of the AC output switch are as follows:
Inverter model
Switch specification
MOD 3000TL3-XH
10A/230V
MOD 4000TL3-XH
10A/230V
MOD 5000TL3-XH
15A/230V
MOD 6000TL3-XH
15A/230V
MOD 7000TL3-XH
15A/230V
MOD 8000TL3-X
20A/230V
MOD 9000TL3-XH
20A/230V
MOD 10KTL3-XH
25A/230V
17
>
Good grounding is good for resisting surge voltage impact and improving
EMI performance. Therefore,you need to ground the wire before connecting
the AC,DC,and communication cables.
>
For a single-machine system.only the PE cable needs to be
grounded;For a multi-machine system,the PE cables of all inverters need to
be connected to the same grounding copper bar to ensure equipotential con-
nection.