6.8 Inverter demand response modes (DRMS)
This series inverter has the function of demand response modes, We use 16-Pin socket as inverter
DRMS connection.
6.8.1 16-Pin socket pin assignment
No.
Description
Remarks
11
DRM 1/5
Relay contact 1 input
12
DRM2/6
Relay contact 2 input
13
DRM3/7
Relay contact 3 input
14
DRM4/8
Relay contact 4 input
15
REF/GEN
GND
16
DRMO/COM
/
6.8.2 Method of asserting demand response modes
Mode
Socket asserted by
shorting pins
Function
DRM 0
14
13
Operate the disconnection device.
DRM 5
9
13
Do not generate power.
DRM 6
10
13
Do not generate at more than 50% of rated power.
DRM 7
11
13
Do not generate at more than 75% of rated power and reduce
the reactive power as far as possible.
DRM 8
12
13
Increase power generation (subject to constraints from other ac-
tive DRMs).
25
DRMS application description
>
Applicable to AS/NZS4777.2:2015 or Commission Regulation (EU)
2016/631.
>
DRMO, DRM5, DRM6, DRM7, DRM8 are available.
Information
CAUTION
WARNING
Damage to the inverter due to moisture and dust penetration
>
Make sure the cable gland has been tightened firmly.
>
If the cable gland are not mounted properly, the inverter can be de-
stroyed due to moisture and dust penetration. All the warranty claim will
be invalid.
Excessive voltage can damage the inverter! External
voltage of DRM PORT don't over +5V.
Summary of Contents for MOD 10KTL3-XH
Page 1: ...Asennus ja k ytt ohje...
Page 19: ...Kuva 5 9 Kaaviokuva invertterin sein asennuksesta...
Page 57: ...Installations och bruksanvisning...
Page 75: ...Figur 5 9 Schema f r v ggmontering av v xelriktaren...
Page 113: ...Operation Manual Installation...
Page 131: ...Fig 5 9 Schematic diagram of inverter wall mounting...
Page 169: ......