Chart 5.10
Wire suggest length:
conductor cross section
max cable length
10AWG
12AWG
Growatt
SPA 4000
TL3 BH-UP
Growatt
SPA 6000
TL3 BH-UP
Growatt
SPA 8000
TL3 BH-UP
Growatt
SPA 5000
TL3 BH-UP
Growatt
SPA 7000
TL3 BH-UP
Growatt
SPA 10000
TL3 BH-UP
88m
59m
70m
50m
44m
35m
55m
37m
44m
31m
27m
22m
AC output terminal and EPS output terminal connection steps as follow:
Step 1: Uninstall the AC terminal as below chart.
Step 2: Thread cables through pressure screw, seal ring, threaded sleeve in sequence,
insert cables into connection terminal according to polarities indicates on it and tighten
the screws.
Chart 5.11
Chart 5.12
Chart 5.13
Step 3: Push threaded sleeve on to connection terminal until both are locked tightly.
Step 4:Plug the socket into AC output terminal
,
clockwise rotation to tighten the
socket, counterclockwise rotation to loosen the socket.
The following diagram shows the AC output terminal of the Australian machine
connection steps, EPS output terminal connection steps consistent with the above steps.
AC output terminal and EPS output terminal connection steps as follow:
Step 1: Uninstall the AC terminal as below chart.
Step 2: Thread cables through pressure screw, seal ring, threaded sleeve in sequence,
insert cables into connection terminal according to polarities indicates on it and tighten
the screws.
Chart 5.14