Chart 5.21
Note:
This diagram is an example for customer who only wants to use the on grid storage
system.The neutral line is necessary
.
Notice:
Ø
If you want to use on gird only, please refer to chart 5.21 Connect with AC grid and
float EPS OUTPUT.
Ø
If you want to use both on gird power and backup power, please refer to chart
5.19and 5.20.Connect with AC grid and EPS OUTPUT like the chart show.
Ø
On grid terminal and off grid terminal can't directly connect together.
Ø
Off Grid terminal can't connect to grid.
Ø
The first start of system needs Grid power.
SPA Inverter
ACGRID
L3
L2
L1
N
L3
N
E
Battery
PE
Electic meter
E
L1
L2
L3
N
L2
L1
Load
RCD
EPS output does not support half-wave load type devices,
such as hair dryers.
19
20
Chart 5.22
5.4.3 Connection of battery terminal
Similar to the traditional inverter connecting, the input of battery can be realized by
using MC4 terminal, the detail steps are as follows:
Step 1: Turn off battery switch.
Step 2: Insert battery panel positive and negative cables into MC4 terminal
,
then
connect positive pole(+) of connection cable to positive pole(+) of battery input
connector, connect negative pole(-) of connection cable to negative pole(-)of battery
input connector.
Please pay attention to battery input voltage and current within permission Limit:
Ø
Max battery voltage: 550V
Ø
Max battery input current: 25A
Ø
Max battery input power : 10000W
Remark:
We suggest you use the cable
≥
4mm2/10 AWG to connect.
Note:
We suggest the distance between battery and SPA no longer than 5m, and The power
line area must be larger than 10AWG.
AC