5.4.7 Connection of DRMS terminal(Australia only)
When SPA is applied to Australia, the DRMS terminals need to be connected, the
connection way appears as follows:
Step1: Unscrew the swivel nut from the cable gland.
Step2: Thread the swivel nut over the “DRMS” cable.
Step3: Press the cable support sleeve out of the cable gland.
Step4: Remove the filler plug from the cable support sleeve.
Step5: Route the “DRMS” cable through an opening in the cable support sleeve.
Step6: Thread the “DRMS” cable through the cable gland.
Step7: Insert the RJ45 plug of the network cable into the “DRMS” pin connector on the
inverter until it snaps into place.
Step8: If no other cables need to be installed, lock the waterproof cover to the inverter
with screws.
Step9: Screw the swivel nut onto the waterproof cover.
Chart 5.31
Chart 5.32
AC
couple
d
RJ45 terminal pin assignment
Method of asserting demand response modes
Note:
1.If the cable such as “NTC” (lead-acid battery temperature sensor) cable is not used,
please do not remove the filler plug from the cable support sleeve.
2.If the power cannot be adjusted, add a 15Kohm,
≥
0.1W resistor between
PIN5
and
PIN6.
5.4.8 Connection of temperature probe for lead-acid battery
When customer using lead-acid battery, the temperature probe of the lead-acid battery
is used to detect the ambient temperature of the lead-acid battery, the battery
temperature cable of the SPA side connection steps are as follows:
Step1: Unscrew the swivel nut from the cable gland.
Step2: Thread the swivel nut over the “NTC” cable.
Step3: Press the cable support sleeve out of the cable gland.
Step4: Remove the filler plug from the cable support sleeve.
Step5: Route the “NTC” cable through a min opening in the cable support sleeve.
Step6: Thread the “NTC” cable through the cable gland.
Step7: Insert the RJ45 plug of the network cable into the “NTC” pin connector on the
inverter until it snaps into place.
Step8: If no other cables need to be installed, lock the waterproof cover to the inverter
with screws.
Step9: Screw the swivel nut onto the waterproof cover.
PIN
assignment for inverter scapable of both charging and discharging
1
2
3
4
5
6
7
8
DRM5
DRM6
DRM7
DRM8
RefGen
COM/DRM0
/
/
MODE Rj45 socket asserted by shorting pins
Requirement
DRM0
DRM5
DRM6
DRM7
DRM8
5
6
1
5
2
5
3
5
4
5
operate the disconnection device
Do not generate power
Do not generate at more than 50% of
rated power
Increase power generation (subject to
constraints from other active DRMs)
Do not generate at more than 75% of
rated power and sink reactive power if
capable