39
40
Note:
1.When EPS Disable & Bypass: OFF, there is no output at the EPS port under any
circumstances;
2.When EPS Enable & Bypass: OFF, the EPS port has no output when there is power grid,
and the EPS port has output when there is no power grid, and the load needs to be
switched through ATS;
3.When EPS Disable & Bypass: ON, the EPS port has output when there is power grid, and
the EPS port has no output when there is no power grid;
4.When EPS Enable & Bypass: ON, there is output at the EPS port under any
circumstances(The normal working mode of EU models).
5.When N_PE Relay ON, the N-PE relay is closed in the off-grid mode(at this time, the
EPS-N line and EPS-PE line will be connected), and disconnected in other modes. When
N_PE Relay OFF, the N-PE relay remains open under any circumstances.
In the EPS you can set, including enable or disable (default is enable), AC voltage(default
is 230V) and frequency (default site 50HZ).
3.Under the Priority, you can see the setup options below after pressing Enter:
Chart 6.8
WorkMode
Stop SOC: 100%
Stop SOC: 5%
WorkMode
Time
WorkMode
Power Rate: 100 %
Power Rate: 100 %
Priority
WorkMode
WorkMode
Opt: Load First
WorkMode
WorkMode
WorkMode
AC CHG: Enable
WorkMode
SC : _ _ _ _
WorkMode
00:00
–
00:00
WorkMode
Save
:
OK
WorkMode
Time
WorkMode
00:00
–
00:00
WorkMode
Save
:
OK
If battery first is choosen
WorkMode
Bat First: OK
If you need to enable AC charging
function , you need key password
Range from 5% to 100%,
and the accuracy is 1%
Range from 5% to 100%,
and the accuracy is 1%
WorkMode
If Grid first is choosen
Grid First: OK
NO
Range from 5% to 100%,
and the accuracy is 1%
Range from 5% to 100%,
and the accuracy is 1%
Press
“
down
”
key to the next item
Press
“
down
”
key to the next item
Choose
“
OK
”
to
the next item
Choose
“
OK
”
to
the next item
Bat First
Grid First
NO
Disable
NO
NO
WorkMode
If Load first is choosen
Load First
:
OK
NO
WorkMode
Stop SOC:xx%
Choose
“
OK
”
to
the next item
Note:
Ø
“
Power Rate” is used to set up power of battery. So different battery may have the
different power, customer need to check the max power of battery.
Ø
Time setting is 24-hour.If the end time is less than beginning time, it defaults to
spanning days.
Chart 6.9
4.Under the Mode Change, you can see the setup options below after pressing Enter:
In the battery type, you can choose lithium battery or lead-acid battery.
Mode Change
WorkMode
Battery
:
Lithium
Lead -acid
WorkMode
Press
“
enter
”
key to
make sure
Press
“
enter
”
key to
make sure
5.Under the DiagnoseFun,you can run“DiagnoseFun”after the installation is completed.
WorkMode
AssemDiag:ON
OFF
WorkMode
Meter1CommFail
WorkMode
Meter1CommTest
WorkMode
Meter1CommPass
WorkMode
M1AssembleTest
WorkMode
M1AssemblePass
WorkMode
BattChrOrDisPass
WorkMode
BattChrOrDisTest
WorkMode
Meter2CommFail
WorkMode
Meter2CommPass
WorkMode
Meter2CommTest
WorkMode
M1AbnormalWire
WorkMode
BattChrOrDisFail
WorkMode
BattChrOrDisFail
Fail
OK
BatFail
M1Fail
OK
Fail
OK
OK
Fail
WorkMode
AssembleDiagOk
Choose “ON” to
the next item
Passed and
displayed for 10s
The test fails
and press OK to
exit
Passed and
displayed for 10s
Only displayed when
RS485-1/-2 set
Meter2 Enable
Passed and
displayed for 10s
Passed and
displayed for 10s
The test fails
and press OK to
exit
The test fails
and press OK to
exit
The test fails
and press OK to
exit
WorkMode
DiagnoseFun
Diagnosis OK and
press OK to exit
Press “enter”
key to make sure
Chart 6.10