background image

44

43

8. Under the Country/Area setting, you can change the safety options of SPA after 
pressing Enter:

      VDE0126

       

         EN50438

WorkMode

VDE0126

       

Chile

WorkMode

      AS4777

       

         AU_sa_network

WorkMode

Europe Area

General Area

Australia Area

      CEI 0-21

CEI 0-16

        

WorkMode

Italy Area

Country/Area

WorkMode

WorkMode

SC : _ _ _ _

If you need to change safety 

options , you need key password

Chart 6.13

Note:

Ÿ

Default safety regulations are set at the factory.

Ÿ

Determine the region according to the factory's safety regulations, LCD can only set 

the corresponding region's safety regulations.

9. Under the Dry Connect setting, you can control the working hours of external water 
heaters, diesel generators and other equipment by setting SPA after pressing Enter:

Heater

WorkMode

WorkMode

D-Time

WorkMode

00:00 

 00:00

WorkMode

Export P: 0000W

WorkMode

00:00 

 00:00

WorkMode

Export P: 0000 W

D-Time

D-Export Power

WorkMode

  D-Time

WorkMode

00:00 

 00:00

D-time

WorkMode

Min.Soc  00%

D-Bat

WorkMode

OnDelay:   00min

WorkMode

MinRun:  000 min

WorkMode

OnDelay:   00min

WorkMode

MinRun:  000 min

WorkMode

Heater: OK

WorkMode

Generator : OK

WorkMode

TurnOff P: 000W

WorkMode

TurnOff P: 000W

D-Mix

WorkMode

Dry Connect

Generator

Disable

           NO

D-Export Power

D-Mix

Save

OK

NO

NO

D-Bat

Save

OK

            NO

    Min.Vbat 00.0V

D-Time: trigger by time
D-Export Power: trigger by output power
D-Mix: trigger by time and output power 

Note:

Ÿ

The D-Bat setting item in the generator option will display different parameters 

according to the type of battery connected. Min.SOC will displayed when a lithium 

battery is connected, and Min.Vbat when a lead-acid battery is connected.

Chart 6.14

Chart 6.15

10.Under the default set, you can see the setup options below after pressing Enter:

Default set is “resume to default setting ”, please don't use it unless it's necessary.

6.5 Communication

6.5.1 Use of USB-A port

USB-A port is mainly for firmware update. Through USB connection, we can quickly 
update the software of machine. You can see USB-A as below:

Note:

 USB is only used for firmware update. Customer can't use it for charging.

Chart 6.16 

Default Set

WorkMode

WorkMode

YES

Press 

enter

 key to 

make sure

Press 

enter

 key more 

than 3 seconds to make sure

Summary of Contents for SPA 10000TL3 BH-UP

Page 1: ...Growatt New Energy Co Ltd 4 13 F Building A Sino German Europe Industrial Park Hangcheng Ave Bao an District Shenzhen China GR UM 245 A 01 86 0755 2747 1942 www ginverter com T E W service ginverter...

Page 2: ...e Use 2 2 Safety Measure 2 3 Symbols introduction on the SPA inverter 1 1 Preface 1 2 Target Group 1 3 Product Description 1 4 Safety Instructions 3 Product Description 4 Unpacking 5 Installation 5 1...

Page 3: ...ter 12 1 Growatt SPA series energy storage machine product specification 12 2 DC input terminal parameter 12 3 Torque 12 4 Appendix 11 Decommissioning 6 Commissioning 12 Product specification 7 1 Star...

Page 4: ...odel it will be dangerous Installer can install energy storage machine of Growatt SPA TL3 BH UP Series rapidly and troubleshooting build communication system through read this manual carefully If you...

Page 5: ...battery use We must make sure ventilation of the service environment and temperature control in order to prevent the danger of battery explosion Battery recommended installation environment must be st...

Page 6: ...uctor terminal Direct Current DC Alternating Current AC Refer to the operating instructions The machine complies with the requirements of the applicable CE guidelines Max output apparent power Nominal...

Page 7: ...ngress Protection Operation Ambient Temperature Certificates Number Growatt SPA 10000TL3 BH UP 10000W 10000VA 3W N PE 230 400Vac 15 2A 50Hz 60Hz 0 8 leading 0 8 lagging 10000W 230 400Vac 50Hz 60Hz 100...

Page 8: ...rew Ground terminal M4 setscrew Installation 5 5 1 Basic installation requirements A The installation location must be suitable for SPA s weight for a long period time B The installation location must...

Page 9: ...pace into account about the dimensions please reference user manual N The Inflammable and explosive dangerous goods must not be placed around battery in case of cause serious danger 5 2 Installation r...

Page 10: ...ge of the cardboard is horizontal 3 Mark four points at the wall via the hole of the paper board then remove the cardboard 4 Drill four 8 holes at the mark point the depth is not less than 55mm 5 Knoc...

Page 11: ...ndicates on it and tighten the screws Chart 5 11 Chart 5 12 Chart 5 13 Step 3 Push threaded sleeve on to connection terminal until both are locked tightly Step 4 Plug the socket into AC output termina...

Page 12: ...g the AC terminal into the inverter AC port Chart 5 15 Chart 5 16 Chart 5 17 Chart 5 18 Chart 5 19 Chart 5 20 The recommended wiring diagram is as follows Note This diagram is an example for gird syst...

Page 13: ...load type devices such as hair dryers 19 20 Chart 5 22 5 4 3 Connection of battery terminal Similar to the traditional inverter connecting the input of battery can be realized by using MC4 terminal th...

Page 14: ...meter user manual Chart 5 23 Chart 5 24 21 Chart 5 25 Chart 5 26 Remark Meter wire 15m in length specification RJ45 standard LAN line one end with 8P modular plug the other connected with transformer...

Page 15: ...l nut over the RS485 cable Step3 Press the cable support sleeve out of the cable gland Step4 Remove the filler plug from the cable support sleeve Step5 Route the RS485 cable through an opening in the...

Page 16: ...re probe for lead acid battery When customer using lead acid battery the temperature probe of the lead acid battery is used to detect the ambient temperature of the lead acid battery the battery tempe...

Page 17: ...ivel nut from the cable gland Step2 Thread the swivel nut over the cable Step3 Press the cable support sleeve out of the cable gland Step4 Remove the filler plug from the cable support sleeve Step5 Ro...

Page 18: ...e period but if you use website settings you can set up to three periods of the priority mode Refer to 6 4 4 Load first Load first is the default mode With inverter in the SPA system energy from inver...

Page 19: ...normal mode otherwise it will go to fault mode 6 2 5 Standby mode If the system hasn t faults while the condition is not qualified SPA would stay at standby mode With inverter in the SPA system batte...

Page 20: ...AU_Ausgrid GT4XXXXXX6 AU_Endeavour GT4XXXXXX7 AU_Ergon_Energy GT4XXXXXX8 AU_Energex GT4XXXXXX9 AU_sa_network GT4XXXXXXA Brazil Brazil GT1XXXXXX5 NULL Brazil 240V NULL Mexico Mexico NULL India India GT...

Page 21: ...ess up button command will go back Workmode depend on the situation If SPA is normal state it will show normal If SPA is standby state it will show as standby etc Some special definitions are explaine...

Page 22: ...ad acid CC maximum battery charge discharge current default is 25A Lead acid CV maximum voltage of single battery default is 14 5V Lead acid Number number of connected batteries default is 12 2 Under...

Page 23: ...cy is 1 Range from 5 to 100 and the accuracy is 1 Press down key to the next item Press down key to the next item Choose OK to the next item Choose OK to the next item Bat First Grid First NO Disable...

Page 24: ...takes effect 2 When the ExportLimit is set to ON and the SingleLimit is ON the phase level export limit function takes effect 3 LoadFstCtrl has two modes SiEn and ThEn If it is set to SiEn the phase l...

Page 25: ...Run 000 min WorkMode OnDelay 00min WorkMode MinRun 000 min WorkMode Heater OK WorkMode Generator OK WorkMode TurnOff P 000W WorkMode TurnOff P 000W D Mix WorkMode Dry Connect Generator Disable NO D Ex...

Page 26: ...3 L1 N N E E Battery PE Electic meter1 L2 L1 L3 L2 UPS Load E L1 L2 L3 N L2 L1 Load L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N METER 485 1 or 485 2 PV Inverter ACGRID L3 L2 L1 N E Electic meter2 Chart 6 19 As t...

Page 27: ...cial website of Growatt Chart 6 21 ShineBus Chart 6 22 47 48 Chart 6 23 Chart 6 24 Chart 6 25 The wiring diagram is as follows 6 5 3 The SPA s monitoring The SPA provide RS485 interface Users can thro...

Page 28: ...necting or disconnecting battery terminals f Determine if battery is inadvertently grounded If inadvertently grounded remove source from ground Contact with any part of a grounded battery can result i...

Page 29: ...t solve the problem BMS COM Fault Communication fault 1 Check the lithium Battery is open or not 2 Check the connection of lithium Battery and inverter is good or not Battery reversed Battery termina...

Page 30: ...ification or not EU Declaration of Conformity 10 With the scope of EU directives 2014 35 EU Low Voltage Directive LVD 2014 30 EU Electromagnetic Compatibility Directive EMC 2011 65 EU RoHS Directive a...

Page 31: ...e 10ms Battery data DC Battery voltage range 100 550V Max charging discharging current 25A Continuous charging discharging power 4000W 5000W 6000W 7000W 8000W 10kW Type of battery lithium battery Lead...

Page 32: ...he Growatt New Energy Technology Co Ltd or dealer orders P N is only for reference and it may be changed Upper cover screws Shell Dc connector M6 screwdriver Grounding screw 1 3Nm 10 8 1bf in 0 7Nm 6...

Page 33: ...to 6 4 4 in the set up surface of Auto Test Press the enter key make sure to start auto test by press enter key 3 seconds The LCD will display the follow message 59 S2 Limit Waiting to start 264 5 V...

Reviews: