14
13
Conductor cross
section
Max cable length
SPA 1000TL BL
SPA 2000TL BL
SPA 3000TL BL
5.2mm^2 10AWG
60m
50m
30m
3.3mm^2 12AWG
40m
30m
20m
The suggest length of the wire
AC output terminal connection steps as follow
:
Step 1
:
Uninstall the AC terminal as above chart
Step 2
:
Thread cables through pressure screw, seal ring, threaded sleeve in sequence,
insert cables into connection terminal according to polarities indicates on it and tighten
the screws.
Table 5.3
Fig 5.10
Fig 5.11
Fig 5.12
Step 3
:
Push threaded sleeve on to connection terminal until both are locked tightly.
Fig 5.13
Fig 5.14
Step 4
:
Plug the socket into AC output terminal
,
clockwise rotation to tighten the
socket, counterclockwise rotation to loosen the socket. The recommended wiring
diagram is as follows:
•
wiring connection.
This diagram is an example for gird system without special requirement on electrical