6.4.4 Work mode set up
•”
•Workmode depend on the situation. If SPA is in normal state, it will show ”normal”. If
SPA is standby state, it will show as “standby” etc.
•Some special definitions are explained, for example: Vb means the voltage of battery.
Cb means the capacity of lithium battery (only lithium battery show this data). Pm means
the monitor power of user.
Down” control command (if pushing “up” button, command will go back).
NOTICE:
Some special definitions:
Parameter:Description
Vb:Battery voltage
Cb:Battery capacity (only for lithium battery)
Pm:Power monitoring (from grid is positive, to grid is negative )
Keep pressing “enter ”for 3S
,
you can enter set up surface
,
in the set up surface you
need hold button.
Enter or ESC 1S for selection, you can see the surface as showing below.
Fig 6.13
If you choose CEI and used SPA inverter in Italy, SPA inverter have Auto Test function.
How to use the Auto test function. Please see the annex.
•Under the Basic Para ,you can see the setup options below after pressing Enter for 1S
:
Fig 6.14
Fig 6.15
In the basic Parameter
,
you can set language
(
English
,
Italian ,German
),
system
time , lead-acid cell charging voltage (default is 58V)
,
discharge low voltage (default is
48V)and lead-acid constant current (default is 60A).
Under the Back Up ,you can see the setup options below after pressing Enter for 1S
:
In the back up you can set EPS ,including enable or disable (default is enable ),AC
voltage(default is 230V) and frequency(default site 50HZ).
Under the Priority
,you can see the setup options below after pressing Enter
:
Basic Parameter
WorkMode
WorkMode
Configuration
WorkMode
MODE Change
WorkMode
Default Set
WorkMode
Priority
WorkMode
BackUp
Press “enter” key more
than 3 seconds into setup
mode
Press “down”
key to the next
item
Press “enter” key
more than 1 seconds to
make sure
Default Set
WorkMode
Auto Test
WorkMode
WorkMode
WorkMode
Language
WorkMode
English
Italian
German
WorkMode
System time
WorkMode
xxD/xxM/xxxxY
WorkMode
Lead-acid CV
WorkMode
58.0 V
WorkMode
Lead-acid CC
WorkMode
60 A
Press “enter” key more
than 1 seconds to make
sure
Press “down”
key to the next
item
Press “enter” key
more than 1 seconds to
make sure
Range from 57.6 to 59.2V,
and the accuracy is 0.1V
Range from 0 to 66A,
and the accuracy is 1A
Basic Parameter
Only display when
battery type is
lead-acid
Only display when
battery type is lead-
acid
WorkMode
Lead-acid LV
WorkMode
48V
Range from 44 to 50V,
and the accuracy is 1V
Only display when
battery type is
lead-acid
WorkMode
BackUp
WorkMode
WorkMode
WorkMode
Backup: Enable
Disable
ACVolt: 230V
240
208
WorkMode
AC Freq: 50 Hz
60
Press “enter” key
more than 1 seconds to
make sure
Press
“
down
”
key to the next item
Press “enter” key
more
than 1 seconds to make
sure
EPS setup