8
Note:
When the battery type set to Li, the setting option 12, 13, 21 will change to display percent.
Note:
When the battery type set as “LI”, the Maximum charge current can't be modified by the user. When the
communication fail, the inverter will cut off output.
Note:
Any questions about communicating with BMS, please consult with Growatt.
3.
Communicating with battery BMS in parallel system
If need to use communicate with BMS in a parallel system, you should make sure to connect the BMS communication
cable between the battery and one inverter of the parallel system. It’s recommended to connect to the master
inverter of the parallel system.
12
Setting SOC point back to utility
source when selecting “SBU
priority” or “Solar first” in program
01
Default 50%, 6%~95% Settable
13
Setting SOC point back to battery
mode when selecting “SBU
priority” or “Solar first” in program
01
Default 95%, 10%~100% Settable
21
Low DC Cut-off SOC.
If self-defined is selected in
program 5, this program can be
set up
Default 20%, 5%~50% Settable