19
28
Address setting
24V model: default 1, 1~255 Settable
48V model: default 1, 1~255 Settable
43
Battery equalization
Battery equalization enable
Battery equalization disable(default)
If “Flooded” or “User-Defined” is selected in program 05, this program
can be set up.
44
Battery equalization Voltage
24V model: default 29.2V, 24.0V~29.2V Settable
48V model: default 58.4V, 48.0V~58.4V Settable
45
Battery equalized time
Default 60min, 5min~900min
Settable
46
Battery equalized timeout
Default 120min, 5min~900min
Settable
47
Equalization interval
Default 30days, 1 days~90 days
Settable
48
Equalization activated
immediately
Equalization activated immediately
on
Equalization activated immediately
off(default)
If equalization function is enabled in program 43, this program can be
setup. If “On” is selected in this program, it’s to activate battery
equalization immediately and LCD main page will shows “
”. If “Off” is
selected, it will cancel equalization function until next activated
equalization time arrives based on program 47setting. At this time,
“
” will not be shown in LCD main page.